AS-B984-101 | Schneider Modicon 800 High-Speed Counting / High-Speed Logical Operation Intelligent Module
Description
Model Interpretation
984 = Modicon 984 platform high-speed intelligent IO series; 101 = 16 input 16 output, load-free detection high-speed counting specification; 100 is a model with the same number of points but with load detection, the hardware appearance is the same, and the firmware circuit is different. Technical Specifications
Position configuration: 16 channels of 24VDC high-speed input, 16 channels of 24VDC transistor output; single-channel input response ≤ 100μs (without filtering), output action ≤ 1ms
Counting specifications: Multi-channel independent high-speed pulse counting, maximum input frequency 100kHz, supports addition and subtraction counting, preset trigger output
Electrical specifications: On-site power supply DC20~28V, single-channel output rated 1A, total module output upper limit 8A, backplane 5V bus power extraction
Installation specifications: Single-slot Eurocard standard rack size, 58 (W) × 267 (H) × 216 (D) mm, net weight approximately 1.65kg
Environmental conditions: Operation 0~60℃, storage and transportation - 40~85℃, humidity < 80% RH without condensation, IP20 cabinet installation
Interface and matching base
Complementary universal terminal base AS-8535-000, compatible with all series of B883, B884, B885 module bases, cannot use dedicated narrow-type terminal base.
Core functions
On-board independent computing unit, high-speed counting, comparison output, fast local hardware execution, does not occupy PLC scanning cycle; when the count value reaches the preset value, it directly drives the local DO output to achieve millisecond-level emergency stop / disconnection; panel multi-channel status LED, respectively indicating channel on/off, counting ready, fault alarm; PLC reads and writes count values and parameters through backplane registers. Applicable scenarios
Packaging production line part counting, wire extrusion metering and speed measurement, high-speed feeding trigger for stamping machines, flow statistics for belt conveyors, high-speed point triggering control for small equipment.
Operation and Maintenance
Plug directly into the Modicon 800 universal I/O slot; if counting is inaccurate, first check the input power ripple and signal line shielding; if output does not act, check the load current; for 101 without load detection, it is impossible to diagnose without no-load condition; special modules such as B885 motion card and B884 temperature control card can be mixed with the same chassis.