140CPS11420
Description
Electrical Ratings
Input (AC)
Nominal Voltage: 115 / 230 V AC (auto‑range)
Operating Range:
115 V: 93 … 132 V AC
230 V: 170 … 276 V AC
Frequency: 47 … 63 Hz (50/60 Hz)
Input Current:
115 V: 1300 mA
230 V: 750 mA
Inrush Current:
115 V: 38 A
230 V: 19 A
Fuse: 2 A, slow‑blow (external)
Rated Power: 130 VA
Output (DC)
Voltage: 5.1 V DC (regulated)
Current (@ 60 °C):
Standalone: 11 A
Summable (parallel): 20 A
Power Dissipation: 6 + (1.5 × Iout) (Iout in A)
Ripple/Noise: ≤ 50 mVpp
Harmonic Distortion: ≤ 10% of fundamental
3 – Protection & Alarm
Internal Protections: Overvoltage, overload, short‑circuit, overtemperature
Alarm Output: 1 × NC (normally closed) relay, 6 A / 220 V (power supply fault)
4 – Indicators
PWR OK (Green LED): ON = output healthy
5 – Environmental
Operating Temperature: 0 °C … +60 °C
Storage Temperature: −40 °C … +85 °C
Humidity: 5% … 93% RH, non‑condensing
Altitude: ≤ 2000 m
Certifications: CE, UL 508, CSA C22.2, FM Class 1 Div. 2
6 – Compatibility
Compatible Racks: All Quantum backplanes (140XBPxxx)
Redundancy: Supports parallel operation (summable) for higher current or redundancy
Get a Quote