Description

SAIA-BURGESS PCD3.C100 B42752170841: PCD3 Four-Slot I/O Expansion Module Holder Product Description

Brand and Product Identification

The SAIA-BURGESS PCD3.C100, with identification reference B42752170841, is an I/O expansion module holder for the Saia PCD3 programmable controller family. The PCD3 prefix identifies the PCD3 controller platform, C100 identifies the four-slot I/O module holder without integrated 24 V DC power supply, and the B42752170841 number is the unit or internal manufacturing reference associated with this holder. The PCD3.C100 accepts four standard PCD3 I/O modules and connects to a PCD3 CPU or another expansion holder through the PCD3 I/O expansion bus.

Product Function and System Role

The PCD3.C100 provides four physical slots and the internal I/O bus connection for standard PCD3 input, output or analog modules. It extends the number of I/O points available to a PCD3 controller by mounting additional cassette-style modules in a DIN rail expansion row. The holder distributes the internal plus 5 V and plus V 24 V module bus to the mounted I/O modules and provides ground and bus connection for the expansion segment. It is a module holder or bus rack, not a CPU, I/O module, communication module, power supply, sensor or field device.

Slot and System Expansion Capacity

The PCD3.C100 has four I/O module slots. PCD3.Mxxxx CPUs can be expanded with PCD3.Cxxx holders to provide additional module positions. Up to 15 PCD3.Cxxx expansion holders can be connected to a PCD3.Mxxx0 CPU, with the PCD3.M3020 CPU not expandable according to the datasheet. This allows a maximum of 64 I/O modules or 1023 digital inputs and outputs in the full PCD3 system. All standard I/O modules can be used in the expansion holders; communication modules or other intelligent modules can only be used in the base CPU slots.

Bus Connection and Current Draw

The PCD3.C100 connects to the CPU or preceding expansion holder through the I/O bus connector or expansion cable. The holder has a port for the CPU or I/O expansion holder connection, a bus connection to the PCD3, ground connection for I/O modules, and an I/O bus for simple modules. Current draw from the internal plus 5 V bus is 10 mA. The internal plus V 24 V bus current draw for the holder is listed in the PCD3 power budget calculation together with the mounted I/O modules. The first slot on the base CPU module is recommended to be left free for future expansion according to PCD3 planning guidance.

Mechanical Construction and Mounting

The PCD3.C100 mounts on a single 35 mm DIN rail. Datasheet dimensions include 130 mm overall length, 28.5 mm and 63.8 mm segment dimensions, 125.8 mm and 67.3 mm mounting or bus dimensions, and 35 mm rail width reference. Holder weight is 420 g. The front layout includes a 5 V internal supply voltage LED indicator, CPU or expansion holder port, ground terminal and I/O module bus slots. The holder clips onto the DIN rail by pressing the lower section against the mounting surface, hooking the lower rail side, then pressing the upper section into place and pushing down to confirm engagement.

Expansion Cables and Accessories

The PCD3.K010 expansion connector connects the I/O bus from a PCD3.M, T or C unit to a PCD3.Cx00 holder and weighs 40 g. The PCD3.K106 expansion cable is 0.7 m long, and the PCD3.K116 expansion cable is 1.2 m long for PCD3.M or T or C to PCD3.Cx00 connection. Slot covers are available for unused PCD3 I/O slots, including part 410475150 with the SBC logo and part 410475020 neutral without logo. PCD3 modules and terminals must be inserted or removed only after disconnecting the Saia PCD controller supply; the external plus 24 V supply for modules must also be disconnected.

Power Budget and Bus Rules

The internal plus 5 V and plus V 24 V load current from I/O modules must not exceed the CPU, RIO or PCD3.C200 holder supply capacity. The PCD3.C200, a four-slot holder with integrated 24 V DC power supply, is used to extend the I/O bus or power a module segment. In single-row installations with a maximum of 15 holders, a PCD3.C200 must be placed after every five PCD3.C100 holders to amplify the bus signal unless the configuration ends with the fifth C100. In multiple-row installations, only three expansion holders can be mounted in a row due to cable length limits, comprising one PCD3.C200 and two PCD3.C100 holders. Up to five PCD3.K106 or K116 cables are permitted in a configuration.

Typical Application Scenarios

Typical applications include expanded PCD3 PLC installations in building automation, HVAC control, production machines, conveyor control, packaging equipment, process monitoring and remote I/O rows where more than the CPU base slots are required. The C100 holder groups four digital input, digital output or analog modules in a DIN rail expansion row connected to the PCD3 CPU by expansion connector or cable.

Installation and Configuration Notes

Installation should follow the Saia PCD3 hardware manual, PCD3.C100 datasheet, PG5 Device Configurator rules and local electrical codes. Mount the holder on the 35 mm DIN rail, connect the expansion bus from the CPU or preceding holder, insert standard I/O modules into the C100 slots, verify module addresses and bus current budget in PG5 software, and connect field wiring to the mounted modules. Do not hot-swap PCD3 modules. Confirm total plus 5 V and plus V current, holder count, cable length, C200 placement requirement and unused slot covers before energizing.

Advantages and Selection Notes

The PCD3.C100 offers four I/O slots, DIN rail mounting, internal bus distribution, 10 mA plus 5 V bus draw, compatibility with standard PCD3 input, output and analog modules, and expansion connector or cable connection to PCD3 CPUs and holders. When selecting a replacement, confirm C100 four-slot holder versus C110 two-slot holder or C200 four-slot holder with integrated power supply, expansion connector or cable requirement, mounted I/O module list, bus current budget and CPU expansion capacity. The PCD3.C100 is an I/O expansion module holder, not a CPU, I/O module, communication module, power supply or sensor; its role is to mount and bus four standard PCD3 I/O modules in a PCD3 expansion row.


Get a Quote