3500/34 TMR Relay Module (Bently Nevada)
Description
Model Interpretation
3500/34‑XX‑XX
3500/34: TMR Relay Module (6‑channel)
1st XX (Configuration):
01: Standard (6 relays, 24 VDC coil)
02: High‑current contacts (5 A resistive)
2nd XX (Certification):
00: Standard
01: CSA/ATEX/IECEx (Zone 2)
Common P/N: 3500/34‑01‑00 (125720‑01)
Technical Parameters
Mechanical
Form Factor: Full‑height module (1 slot)
Dimensions (H×W×D): 241 mm × 24.4 mm × 242 mm
Weight: ~0.8 kg
Installation: Any slot in 3500 rack; hot‑swappable
Power Consumption: 6 W typical
Electrical – Relay Outputs
Channels: 6 independent Form C (NO/NC/COM)
Contact Rating:
Resistive: 5 A @ 30 VDC
Inductive: 3 A @ 30 VDC
Coil Voltage: 24 VDC (supplied by rack backplane)
Response Time: <25 ms
Voting Logic: 2‑out‑of‑3 TMR per relay (3 independent circuits)
Fault Isolation: Single‑channel failure does not affect output
Environmental
Operating Temp: −30°C to +65°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Certifications: SIL 3, CE, UL, CSA, ATEX/IECEx (Zone 2)
Compliance: API 670, IEC 61508
Compatibility
Rack: 3500/05 (all slots)
Monitors: All 3500 series (40M, 42M, 44M, etc.)
Software: 3500 Rack Config v3.3+ (relay mapping, logic setup)
System: TMR‑configured 3500 systems (critical protection)
Core Functions
TMR Fault Tolerance: Three independent processing paths per relay; 2‑out‑of‑3 voting ensures valid output even with one channel fault.
6‑Channel Isolated Relays: Map any alarm/danger from monitors to relays for DCS/PLC trip interlocks.
Fail‑Safe Operation: Relays de‑energize on fault/power loss (safe state for shutdowns).
Diagnostics & Bypass: Self‑check, relay coil monitoring, and channel bypass for maintenance.
High‑Speed Switching: <25 ms response for fast machine protection.
Applications
Power Generation: Steam/gas turbine emergency shutdown (ESD), generator trip, BFP protection.
Oil & Gas: Centrifugal compressor anti‑surge, high‑speed trip, process safety interlocks.
Heavy Industry: Critical motor, gearbox, and fan vibration trip systems.
Safety‑Critical TSI: SIL 3‑rated turbine supervisory instrumentation for high‑integrity plants.
Redundant Protection: Any rotating machinery requiring zero single‑point failure in alarm/shutdown paths.
Get a Quote