3500/33 16-Channel Relay Module (Bently Nevada)
Description
Model Interpretation
3500/33: 16‑Channel Relay Module
1st XX (Configuration):
01: Standard (SPDT, epoxy‑sealed, arc suppression)
2nd XX (Certification):
00: Standard
01: CSA/ATEX/IECEx (Zone 2)
Common P/N:
3500/33‑01‑00 (149986‑01, 162291‑01)
3500/33‑01‑01 (certified)
Technical Parameters
Mechanical
Form Factor: Full‑height (1 front slot + 1 rear slot)
Dimensions (H×W×D): 241 mm × 24.4 mm × 242 mm
Weight: ~0.7 kg
Power Consumption: 5.8 W typical
Electrical – Relays
Channels: 16 independent SPDT outputs
Contact Rating:
5 A @ 250 VAC
5 A @ 300 VDC
Min Switched Current: 100 mA @ 12 VDC
Arc Suppression: 250 Vrms standard
Contact Life: 100,000 cycles (5 A, 24 VDC)
Operation: 4‑channel groups, selectable Normally Energized / De‑energized
Electrical – Logic & I/O
Logic: AND/OR, voting, latching per channel
Inputs: Any Alert/Danger/Not OK from rack modules
LEDs: OK, TX/RX, 16×CH ALARM
Software: 3500 Rack Config v3.3+; Data Acquisition v2.40+
Environmental
Operating Temp: −30°C to +65°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Certifications: SIL 2, CE, UL, CSA, ATEX/IECEx (Zone 2)
Sealing: Epoxy‑sealed for harsh environments
Compatibility
Rack: 3500/05 (right of TDI/interface)
System: All 3500 monitors (vibration, displacement, speed)
Safety: SIL 2 rated for machinery protection loops
Core Functions
16 Independent Relays: High‑density output for large TSI systems (turbines, compressors).
Flexible Voting Logic: Each channel programmed with AND/OR/latch using any rack alarm status.
Failsafe Operation: Configurable de‑energized state for safety trips.
Epoxy Sealing & Arc Protection: Reliable in high‑noise, oily, humid industrial areas.
Front‑Panel Diagnostics: Quick status for module health, comms, and each relay channel.
Applications
Power Generation: Steam/gas turbines, generators, BFP (multiple alarm/trip points).
Oil & Gas: Compressors, pumps, turbines (high‑channel‑count protection).
Heavy Industry: Large motors, gearboxes, process machinery interlocks.
TSI & Safety: Vibration, displacement, speed monitoring with many shutdowns.
DCS/PLC Integration: 16 relay outputs to plant control systems for remote annunciation/tripping.
Get a Quote