1900/55 Fan Monitor (Bently Nevada)
Description
Model Interpretation
1900/55‑XX‑XX‑XX‑XX
1900/55: Base model (4‑channel fan monitor, vibration + speed + temperature)
1st XX (Power):
01: 115/230 VAC (50/60 Hz)
02: 85–264 VAC universal
2nd XX (Relays):
00: Standard relay configuration
3rd XX (Options):
01: With speed monitoring
00: No speed monitoring
4th XX (Certification):
01: CSA/ATEX certified
Common part number: 137250‑01.
Technical Parameters
Mechanical
Form Factor: Stand‑alone, panel‑mount
Dimensions (H×W×D): 337 mm × 295 mm × 130 mm
Weight: ~3.18 kg
Enclosure: Industrial metal, IP20
Inputs
Vibration Channels: 4 seismic (accelerometer/velocity) inputs
Speed Channel: 1 tachometer input (0–10 kHz)
Temperature Inputs: 2 RTD (PT100) inputs
Sensor Compatibility: Trendmaster® 2000 accelerometers, 3300 series proximity probes, PT100 RTDs
Vibration Range: 0–50 mm/s peak velocity (low‑frequency optimized: 1–1 kHz)
Speed Range: 0–60,000 RPM
Accuracy: ±1.5% FS (vibration), ±0.1% FS (speed)
Outputs
Relays: 4 × DPDT (Alert, Danger, Speed, Temperature); 5 A @ 250 VAC
Analog Outputs: 4 × 4–20 mA (isolated, for vibration/speed/temperature)
Buffered Output: BNC (raw vibration signal)
Power & Environmental
Power: 115/230 VAC or 85–264 VAC universal
Power Consumption: ~15 W
Operating Temp: −20°C to +60°C
Humidity: 5%–95% RH, non‑condensing
Display: LCD (real‑time values, alarm status)
Status LEDs: OK, Alert, Danger, Fault
Communications
Protocol: Modbus RTU (RS‑485)
Data: Vibration, speed, temperature, alarm status
Core Functions
4‑Channel Low‑Frequency Vibration Monitoring: Optimized for fan gearboxes and large rotating assemblies.
Integrated Speed & Temperature Monitoring: Comprehensive protection for fan systems.
Dual Alarm Thresholds: Independent Alert/Danger for each channel with adjustable delays.
Modbus RTU Communication: Remote monitoring and configuration via RS‑485.
Stand‑Alone Operation: No rack system required; ideal for field installation.
Applications
Power Generation: Cooling tower fans, boiler fans, air handling units.
Oil & Gas: Process fans, blowers, and large auxiliary equipment.
HVAC & Water Treatment: Aeration blowers, ventilation fans, dust collectors.
Manufacturing: Conveyor fans, large cooling fans, and general‑purpose rotating machinery.
Get a Quote