1900/27 Vibration Monitor (Bently Nevada)
Description
Model Interpretation
1900/27‑XX‑XX
1900/27: Base model (single‑channel seismic monitor, 4‑20 mA output, no TIM)
First XX (Power):
00: 24 VDC (18–36 VDC)
01: 115/230 VAC (50/60 Hz)
02: 85–264 VAC / 110–370 VDC (universal)
03: 24 VDC + intrinsically safe (IS)
Second XX (Options):
00: No extra options
Common part number: 141486‑01
Technical Parameters
Mechanical
Form Factor: Stand‑alone, wall‑mount
Dimensions (H×W×D): 132 mm × 132 mm × 71.1 mm
Weight: ~0.4 kg
Enclosure: Industrial plastic, IP20 (front)
Inputs
Channel: 1 dynamic seismic input (accelerometer)
Sensor Compatibility: Trendmaster® 2000 accelerometers (100 mV/g sensitivity)
Measurement: Vibration velocity (peak)
Frequency Response: 8 Hz (–3 dB high‑pass) to >4 kHz (low‑pass)
Range: 0–50 mm/s (0–2 in/s) peak velocity, software‑selectable
Accuracy: ±1% full‑scale
Outputs
Analog Output: 4‑20 mA (isolated, proportional to vibration value)
Relays: 2 × DPDT (Alert, Danger); 5 A @ 250 VAC / 30 VDC
Buffered Output: BNC (raw transducer signal)
No TIM Interface (use 1900/25 for Trendmaster® 2000 system connection)
Power & Environmental
Power: 24 VDC, universal AC/DC, or 115/230 VAC (per model)
Power Consumption: ~8 W
Operating Temp: −40°C to +70°C
Humidity: 5%–95% RH, non‑condensing
Status LEDs: OK, Alert, Danger, Fault
Display: LCD (real‑time value, ~0.8 s refresh)
Communications
No Modbus/Ethernet
No TIM (Trendmaster® 2000 interface)
Core Functions
Single‑Channel Seismic Monitoring: Measures bearing‑housing vibration via accelerometers.
Dual Alarm Thresholds: Independent Alert (warning) and Danger (trip) with adjustable delay (0.1–30 s).
4‑20 mA Analog Output: Direct interface to DCS/PLC for remote trending and control.
Local Indication & Diagnostics: LCD readout + LED status; sensor fault detection (open/short/out‑of‑range).
Stand‑Alone Operation: No system required; ideal for local machinery protection.
Applications
General Industry: Pumps, fans, blowers, motors (bearing‑housing vibration).
Oil & Gas: Auxiliary equipment, non‑critical compressors.
Power: Cooling tower pumps, boiler fans, small turbines.
Retrofit Projects: Replaces older seismic monitors; preferred when 4‑20 mA signal is required.
Get a Quote