1900/65A General Purpose Equipment Monitor (Bently Nevada)
June 02, 2026

1900/65A General Purpose Equipment Monitor (Bently Nevada)

Product Description The 1900/65A is a compact, standalone, cost‑effective multi‑parameter monitor for general‑purpose rotating and reciprocating machinery. It integrates 4 dynamic signal inputs (vibration/position/speed) + 4 temperature inputs into a single unit, serving as an economical alternative to rack‑based 3500 systems for non‑critical but essential assets. It provides continuous condition monitoring, alarm/trip protection, and seamless DCS/PLC integration, widely used in oil & gas, power, and general industry.

Description

Model Interpretation

1900/65A‑XX‑XX‑XX‑XX‑XX
  • 1900/65A: Base model (general‑purpose equipment monitor)

  • 1st XX (Power):

    • 00: 24 VDC

    • 01: 115/230 VAC

  • 2nd XX (Communications):

    • 00: No comms

    • 01: Modbus (RS‑485)

    • 02: Modbus/TCP (Ethernet)

  • 3rd XX (Relays):

    • 00: 6 relays (standard)

    • 03: 6 relays + intrinsically safe (IS) barriers

  • 4th XX (Approvals):

    • 00: None

    • 01: CSA/NRTL/C

    • 02: ATEX/IECEx (Zone 2)

  • 5th XX (Display):

    • 00: Standard LCD

  • Common part numbers: 167699‑02, 1900/65A‑01‑02‑00‑01‑00.

Technical Parameters

Mechanical

  • Form Factor: Standalone, wall‑mountable

  • Dimensions (H×W×D): 196 mm × 160 mm × 108 mm

  • Weight: ~1.36 kg

  • Enclosure: Industrial plastic, IP20 (front)

Inputs

  • Dynamic Inputs (4 Ch):

    • Proximity (eddy‑current): 3300XL series, −24 VDC bias

    • Velomitor (velocity): 100 mV/in/s

    • Accelerometer (acceleration): 2‑wire/3‑wire, 100 mV/g

    • Keyphasor (speed): TTL/HTL, 1–10,000 RPM

    • Frequency Response: 0.5 Hz–25 kHz; 4‑pole HP/LP filters

  • Temperature Inputs (4 Ch):

    • Thermocouple: E, J, K, T

    • RTD: 2‑wire/3‑wire Pt100

  • Resolution: 24‑bit ADC; Accuracy: ±1% FS

Measurement Ranges

  • Vibration (Displacement): 0–500 μm (0–20 mils)

  • Vibration (Velocity): 0–50 mm/s (0–2 in/s)

  • Vibration (Acceleration): 0–50 g (peak)

  • Speed: 1–10,000 RPM

  • Temperature: −200°C to +850°C (sensor‑dependent)

Outputs

  • Relays: 6 × DPDT, 5 A @ 250 VAC / 30 VDC (resistive); programmable Alert/Danger/OK logic

  • 4–20 mA Analog: 4 channels (scaled to any input variable)

  • Buffered Sensor Outputs: 4 × BNC (raw signal, short‑circuit protected)

  • Event Log: 200‑entry (time‑stamped alarms/faults)

Power & Environmental

  • Power: 24 VDC (18–30 VDC) or 115/230 VAC (50/60 Hz)

  • Power Consumption: ~15 W

  • Operating Temp: −40°C to +70°C

  • Storage Temp: −40°C to +85°C

  • Humidity: 5%–95% RH, non‑condensing

  • Status LEDs: OK, Alert, Danger, Fault

Communications

  • Serial: RS‑232/485 (Modbus RTU)

  • Ethernet: Modbus/TCP (optional)

  • Software: 1900 Configuration Software (v5.0+); System 1 compatible

Core Functions

  • Multi‑Input Integration: Combines vibration, position, speed, and temperature in one unit (no separate modules).

  • 4 Dynamic + 4 Temperature Channels: Flexible mapping for motors, pumps, fans, and compressors.

  • Dual Alarm Thresholds: Independent Alert (warning) and Danger (trip) per channel with 0.1–30 s delay (prevents false trips).

  • 6 Programmable Relays: Map any channel’s status to relays for local annunciation or ESD.

  • 4–20 mA Scaled Outputs: Direct interface with DCS/PLC for remote monitoring.

  • Buffered BNC Outputs: Raw sensor signals for oscilloscope diagnostics.

  • Built‑In Diagnostics: Sensor/cable fault detection, over/under‑range, and module self‑check.

  • Standalone Operation: No rack required; wall‑mountable for field installation.

  • Modbus Connectivity: Integrates with SCADA/System 1 for centralized monitoring.

Applications

  • Oil & Gas: Pumps, fans, blowers, and small compressors (non‑critical rotating equipment).

  • Power Generation: Auxiliary motors, boiler fans, and cooling tower pumps.

  • Petrochemical/Refining: General‑purpose machinery (mixers, agitators, conveyors).

  • Water/Wastewater: Centrifugal pumps, aeration blowers.

  • Manufacturing: Machine tools, conveyors, and material handling equipment.

  • HVAC: Large fans and chillers in commercial buildings.

Usage & Maintenance

  • Installation: Wall‑mount; wire sensors to rear terminals; connect power and comms.

  • Configuration: Use 1900 Software; set channel type, range, thresholds, and output scaling.

  • Maintenance: Inspect wiring annually; calibrate every 2–3 years; no internal consumables.

  • Compatibility: Replaces legacy 1900/65; compatible with 3300/3300XL sensors and System 1 software。


Get a Quote