1. Product Overview
2. Key Specifications
Output Channels: 8 fully galvanic isolated analog output channels
Signal Type: 4–20mA DC analog output, compatible with HART 5/6/7 protocol
Isolation: Channel-to-channel & channel-to-ground full isolation; 600 VAC for 1 minute
Accuracy & Resolution: ±0.05% full scale; 13-bit resolution
Max Output Load: 750 Ω
HART Communication: 1200 baud rate; 2 messages per second per channel; max transmission distance 3030m
Power Supply: 24VDC backplane power (±5% tolerance); power consumption ≤7W
Environmental: Operating Temp: -20°C ~ +70°C; Storage Temp: -40°C ~ +85°C; Humidity: 5%–95% non-condensing; ISA S71.04 Class G3 (harsh industrial environment)
Physical & Installation: Dimensions (H×W×D): 102×45×104 mm (approx.); Weight: approx. 284 g; Mounting: DIN rail baseplate; Hot-swappable design
Certifications: CE, UL, ATEX, CSA (Class I Div2 / Zone 2, compliant with industrial safety standards)
3. Core Features
Dual-module hot redundant configuration (master/tracker) with seamless automatic switching, no signal interruption or loss
Full channel isolation effectively eliminates ground loops and industrial electromagnetic interference, ensuring stable signal output
Built-in independent HART modem per channel, supporting remote configuration, calibration and device diagnostics for HART-enabled actuators
Hot-swap capability: Allows module replacement without disconnecting field wiring, power or communication lines, avoiding system downtime
Fault-safe configurable: Supports custom fault actions (hold last value / drop to 0mA) to ensure process safety when module fails
Rugged aluminum housing, designed for harsh industrial environments, with strong vibration and EMI resistance
Compatible with both standard 4–20mA actuators and HART smart valve positioners, supporting mixed configuration
4. Matching Accessories
5. Applications
Input Channels: 32 discrete input channels (2-wire input for each channel)
Signal Type: Digital discrete signals; supports multiple voltage ranges
Input Voltage Range: 15–60 VDC, 120 VAC/125 VDC, 240 VAC (configured via termination assemblies)
Input Current: 2.2 mA (typical) at 30 VDC input
Communication: 2 Mbps redundant module fieldbus, communicates with associated FCM or FCP
Power Supply: 24VDC backplane power (±5% tolerance, -10% lower limit); maximum power consumption ≤3W
Environmental: Operating Temp: -20°C ~ +70°C; Storage Temp: -40°C ~ +85°C; Humidity: 5%–95% non-condensing; ISA S71.04 Class G3 (harsh industrial environment)
Physical & Installation: Dimensions (H×W×D): 102×45×104 mm (approx.); Weight: approx. 284 g; Mounting: DIN rail baseplate; Hot-swappable design
Certifications: CE, UL, ATEX, CSA (compliant with industrial safety standards)