FBM216 Basic Information Model: FBM216 Manufacturer: Foxboro / Schneider Electric System: I/A Series DCS & Evo Compact 200 I/O Type: 8-Channel Redundant Isolated HART Analog Input Module Technical Specifications Input Channels: 8 isolated analog input channels Signal Type: 4–20mA DC with HART protocol support Galvanic Isolation: Group-to-ground isolation Withstand Voltage: 600 VAC for 1 minute Resolution: 16-bit Sigma-Delta ADC Accuracy: ±0.03% of full scale Input Impedance: Approximately 61.5 Ω HART Communication: 1200 baud rate, 2 messages per second per channel Max HART Cable Distance: 3030 meters Power Supply: 24VDC backplane power Power Consumption: ≤ 7 W Operating Temperature: -20°C ~ +70°C Storage Temperature: -40°C ~ +85°C Humidity: 5%–95% non-condensing Environmental Grade: ISA S71.04 Class G3 Certifications: CE, UL, ATEX, CSA

Description

FBM216

Basic Information

Model: FBM216

Manufacturer: Foxboro / Schneider Electric

System: I/A Series DCS & Evo Compact 200 I/O

Type: 8-Channel Redundant Isolated HART Analog Input Module

Technical Specifications

Input Channels: 8 isolated analog input channels

Signal Type: 4–20mA DC with HART protocol support

Galvanic Isolation: Group-to-ground isolation

Withstand Voltage: 600 VAC for 1 minute

Resolution: 16-bit Sigma-Delta ADC

Accuracy: ±0.03% of full scale

Input Impedance: Approximately 61.5 Ω

HART Communication: 1200 baud rate, 2 messages per second per channel

Max HART Cable Distance: 3030 meters

Power Supply: 24VDC backplane power

Power Consumption: ≤ 7 W

Operating Temperature: -20°C ~ +70°C

Storage Temperature: -40°C ~ +85°C

Humidity: 5%–95% non-condensing

Environmental Grade: ISA S71.04 Class G3

Certifications: CE, UL, ATEX, CSA

Key Features

Designed for dual module hot redundant configuration.

Automatic master/standby seamless switching without signal interruption.

Each channel supports standard 4–20mA transmitters and HART smart instruments.

Built-in independent HART modem for remote configuration, calibration and diagnosis.

Supports hot-swap replacement during system running.

High anti-interference performance for industrial harsh environment.

Matching Accessories

Termination Assembly: P0916BX / P0926TD

Redundancy Adapter: P0917XQ

Connection Cable: P0916DA series

Application

Used for redundant signal collection of pressure, flow, level and temperature.

Suitable for critical process loops in chemical, petrochemical, power, oil & gas and water treatment DCS systems.