FBM214b/216b
May 13, 2026

FBM214b/216b

FBM214B / FBM216B Basic Information Manufacturer: Foxboro / Schneider Electric System: I/A Series DCS Compact 200 I/O Module Type: 8-Channel Isolated HART 4–20mA Analog Input Model Definition FBM214B: Standard Non-Redundant HART AI Module FBM216B: Redundant Pair HART AI Module Common Technical Specifications Number of Channels: 8 fully isolated analog input channels Signal Type: 4–20mA DC, HART protocol compatible Galvanic Isolation: Channel-to-channel and channel-to-ground isolation Isolation Withstand: 600 VAC for 1 minute ADC Resolution: 16-bit Sigma-Delta Basic Accuracy: ±0.03% Full Scale Input Impedance: 282Ω (external powered) / 302Ω (internal powered) HART Performance: 2 messages per second per channel Max HART Cable Length: 3030 m Loop Supply Voltage: 24VDC ±10%, per channel current limited Power Consumption: ≤7 W Operating Temperature: 0°C ~ +60°C Storage Temperature: -40°C ~ +85°C Humidity: 5%–95% non-condensing Environmental Grade: ISA S71.04 Class G3 Certifications: CE, UL, ATEX, CSA Difference Between FBM214B and FBM216B FBM214B Working Mode: Single module non-redundant Application: Ordinary non-critical process loops Termination Assembly: RH924JH / P0924JH FBM216B Working Mode: Dual module hot redundant, automatic master/standby switch Application: Important critical loops requiring no downtime Support full system redundancy and hot-swap replacement

Description

FBM214B / FBM216B

Basic Information

Manufacturer: Foxboro / Schneider Electric

System: I/A Series DCS Compact 200 I/O

Module Type: 8-Channel Isolated HART 4–20mA Analog Input

Model Definition

FBM214B: Standard Non-Redundant HART AI Module

FBM216B: Redundant Pair HART AI Module

Common Technical Specifications

Number of Channels: 8 fully isolated analog input channels

Signal Type: 4–20mA DC, HART protocol compatible

Galvanic Isolation: Channel-to-channel and channel-to-ground isolation

Isolation Withstand: 600 VAC for 1 minute

ADC Resolution: 16-bit Sigma-Delta

Basic Accuracy: ±0.03% Full Scale

Input Impedance: 282Ω (external powered) / 302Ω (internal powered)

HART Performance: 2 messages per second per channel

Max HART Cable Length: 3030 m

Loop Supply Voltage: 24VDC ±10%, per channel current limited

Power Consumption: ≤7 W

Operating Temperature: 0°C ~ +60°C

Storage Temperature: -40°C ~ +85°C

Humidity: 5%–95% non-condensing

Environmental Grade: ISA S71.04 Class G3

Certifications: CE, UL, ATEX, CSA

Difference Between FBM214B and FBM216B

FBM214B

Working Mode: Single module non-redundant

Application: Ordinary non-critical process loops

Termination Assembly: RH924JH / P0924JH

FBM216B

Working Mode: Dual module hot redundant, automatic master/standby switch

Application: Important critical loops requiring no downtime

Support full system redundancy and hot-swap replacement

Key Features

Supports both conventional 4–20mA transmitters and HART smart instruments.

Independent HART modem per channel for remote configuration, calibration and diagnosis.

High galvanic isolation avoids ground loop interference and field noise.

Industrial G3 rugged design for long-term stable operation.

Both models support hot swap under corresponding system configuration.

Application

Suitable for pressure, flow, level, temperature HART instrument signal collection.

Widely used in chemical, petrochemical, power, oil & gas and water treatment DCS projects.