FBM212
Description
FBM212
Basic Information
Model: FBM212(Part No.: P0914XL / RH914XL)
Manufacturer: Foxboro / Schneider Electric
System: I/A Series DCS, Compact 200 Series I/O
Type: 14-Channel Isolated Thermocouple/mV Differential Input Module
Status: In service, supports redundancy and hot swap
Application: Industrial temperature measurement (chemical, power, oil & gas)
Foxboro FBM212 模块
Specifications
Input Channels
Quantity: 14 differential isolated thermocouple/mV input channels + 1 RTD cold-junction compensation channel
Signal Types:
Thermocouple: B, E, J, K, N, R, S, T (isolated, non-grounded only)
mV: -10.5 ~ +69.5 mV DC
Input Impedance: 10 MΩ (differential)
Isolation: Channel-to-ground galvanic isolation (600 VAC for 1 minute); channel-to-channel non-isolated
Accuracy (at 25°C)
mV Input: ±0.03% of span (±27 μV)
Thermocouple: ±0.25°C conformity
RTD Reference: ±0.25°C conformity; ±0.50°C measurement accuracy
Temperature Coefficient: ±50 ppm/°C
A/D Conversion
Type: Multiplexed Σ-Δ (sigma-delta)
Update Rate: Configurable, minimum 500 ms
Filtering: Configurable integration period for noise rejection (50/60 Hz)
Power
Supply: 24 VDC (redundant), -10% ~ +5%
Consumption: ≤ 3 W
Environmental
Operating Temp: -20°C ~ +70°C
Storage Temp: -40°C ~ +70°C
Humidity: 5%–95% non-condensing
Rating: ISA S71.04 Class G3 (harsh environment)
Physical
Dimensions: 114 × 45 × 102 mm (H×W×D)
Weight: 284 g (approx.)
Mounting: 200 Series baseplate (DIN rail / 19” rack)
Key Features
14-Channel T/C or mV Input: High-density temperature/mV acquisition.
Built-in Cold-Junction Compensation: Termination assembly-integrated 100Ω Pt RTD (IEC 751 Class B) for accurate cold-junction sensing.
Thermocouple Burnout Detection: Up-scale indication on open circuit.
High Noise Rejection: Σ-Δ ADC with configurable filters for industrial EMI.
Redundancy & Hot Swap: Supports redundant Fieldbus and online replacement.
Robust Construction: Extruded aluminum housing for harsh environments.
Compatible Accessories
Termination Assembly (TA): RH916BV (14-channel, compression terminals)
Cables: RH916FG (0.5m) / RH916FH (1m) / RH916FJ (3m) / RH916FK (5m) / LSZH options available
Application Notes
Use for: Non-grounded thermocouples or mV transmitters.
Do not use for: Grounded thermocouples (use FBM202 instead).
Typical Loops: Furnace, reactor, boiler, and turbine temperature monitoring.

Get a Quote