FBM207
Description
FBM207 (P0914TD)
Basic Information
Part Number: FBM207 (P0914TD)
Manufacturer: Foxboro / Schneider Electric
Series: I/A Series DCS
Module Type: 16-Ch Isolated Voltage Monitor / Contact Sense Input Module
Function: Monitors DC voltage or contact closure status; 3 variants available
Status: Original spare part, available
Variants
FBM207: DC voltage monitor (15–60VDC logic)
FBM207b: 24VDC contact sense
FBM207c: 48VDC contact senseparesource.schneider-electric.com
Specifications
I/O Channels
16 isolated input channels (channel-to-channel & channel-to-ground isolation)
Isolation: >500VDC 光电隔离
Input (Voltage Mode, FBM207)
Logic 1 (On): 15–60VDC
Logic 0 (Off): 0–5VDC
Input Current: 1.4mA (typical @5–60VDC)
Source Resistance: ≤1kΩ (On, 15VDC); ≥100kΩ (Off, 60VDC)paresource.schneider-electric.com
Input (Contact Mode, FBM207b/c)
Open-circuit Voltage: 24VDC±15% (207b); 48VDC±15% (207c)
Short-circuit Current: 3.2mA (typical)
Logic 1 (On): ≤1kΩ
Logic 0 (Off): ≥100kΩparesource.schneider-electric.com
Performance
Response Time: <10ms
Filter/Debounce: Configurable 0/4/8/16/32ms
Pulse Count: No loss up to 250Hz
Power
Supply: 24VDC±5%/−10% (redundant)
Consumption: ≤3W
Heat Dissipation: ≤5.5W
Environmental
Operating Temp: −20°C to +70°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95%, non-condensing
Vibration: 7.5m/s² (5–500Hz)
Rating: ISA S71.04 Class G3 (Harsh)
Certifications: CE, UL, ATEX, CSA
Physical
Dimensions: 104 × 45 × 114mm (H×W×D)
Weight: ~0.28kg
Mounting: DIN rail
Protection: IP20
Key Features
16 galvanically isolated channels for noise immunity
Three variants for 15–60VDC, 24VDC or 48VDC field signals
Configurable debounce for contact bounce suppression
Short-circuit protection per channel
Hot-swap compatible in redundant systems
G3 harsh-environment rated
Compatible Components
Termination Assembly: P0914TE (for 120/240VAC inputs)
Connection Cable: P0916DC (3m standard, up to 30m optional)
Applications
Chemical, petrochemical, power, oil & gas, water treatment
Monitoring limit switches, solenoid valves, pressure/level switches
Detecting contact closure or DC voltage status in I/A Series DCS

Get a Quote