DM400YT
Description
Foxboro DM400YT (FBM17) – Contact/DC Input/Output Module
Product Overview
Model: DM400YT (FBM17)
Type: 16-channel isolated contact/DC digital input/output expansion module
System: Foxboro I/A Series DCS (expansion for FBM09)
Core Specifications
Input Type: Dry contact / 5–30VDC (sink/source)
Output Type: Dry contact relay, 30VDC / 250VAC, 2A per channel
Channel Count: 16 (8 input / 8 output, isolated)
Isolation: 250VACrms (channel-to-channel, channel-to-ground)
Response Time: ≤8ms (input); ≤10ms (output relay)
Backplane Power: 24VDC ±10%
Power Consumption: ≤3.8W
Operating Temp: 0°C to +55°C (32°F to 131°F)
Storage Temp: -40°C to +85°C (-40°F to 185°F)
Humidity: 5%–95% RH, non-condensing
Dimensions (D×W×H): 18.0" × 6.25" × 1.5"
Weight: ~0.9 kg (2.0 lbs)
Hot Swap: Supported (online replacement)
Diagnostics: Open/short detection, channel LED, relay coil monitoring
Installation & Wiring
Mounting: Single-slot vertical install in I/A 100-series chassis; ≥50mm top/bottom clearance for airflow.
Cable: Shielded twisted pair (18–22 AWG); max length 250m (I/O).
Shielding: Shield grounded at control room end only; avoid ground loops.
Separation: Keep DC I/O ≥30cm from AC/high-voltage cables.
Terminals: Torque to 0.8–1.0 N·m; use ferrules on stranded wire.
ESD: Anti-static wristband required; do not touch gold edge connectors.
Output Load: Max 2A/channel; use freewheeling diodes for inductive loads.
Operation & Maintenance
LED Indicators:
PWR: Green = Backplane power good
RUN: Green blink = Normal communication
FAULT: Red = Channel fault, relay overload, or comm error
Redundancy: Supports dual-module redundant pairing; switchover <50ms.
Maintenance:
Inspect/retorque terminals annually.
Clean chassis/module dust every 6–12 months.
End-of-life: Discontinued; no field repair – replace with spare.
Compatibility
Direct Replacement: FBM17, DM400YT-0C
System Compatibility: I/A Series 100-series; works with CP10/30/60 controllers.
Mate Module: FBM09 (CM400YK) – main 8DI/8DO module.
Upgrade Alternative: FBM247 (I/A 200-series, Ethernet-based 16-channel DC I/O).

Get a Quote