SIEMENS DEVICENET 5136-DNS-200S 6ES7138-4CB11-0AB0: DeviceNet Scanner and ET 200S Power Module Product Description
November 17, 2026

SIEMENS DEVICENET 5136-DNS-200S 6ES7138-4CB11-0AB0: DeviceNet Scanner and ET 200S Power Module Product Description

This product record covers two related automation components associated with a Siemens or PLC-based DeviceNet control assembly: the 5136-DNS-200S DeviceNet scanner module and the Siemens 6ES7138-4CB11-0AB0 SIMATIC ET 200S PM-E power module. The 5136-DNS-200S catalog number follows the ProSoft Technology scanner module numbering family, although some distributor records list it under Siemens automation system compatibility. The 6ES7138-4CB11-0AB0 is a Siemens SIMATIC DP ET 200S power module, PM-E DC24 to 48 V or AC24 to 230 V, with diagnostics and a replaceable fuse.

Description

已思考

SIEMENS DEVICENET 5136-DNS-200S 6ES7138-4CB11-0AB0: DeviceNet Scanner and ET 200S Power Module Product Description

Brand and Product Identification

This product record covers two related automation components associated with a Siemens or PLC-based DeviceNet control assembly: the 5136-DNS-200S DeviceNet scanner module and the Siemens 6ES7138-4CB11-0AB0 SIMATIC ET 200S PM-E power module. The 5136-DNS-200S catalog number follows the ProSoft Technology scanner module numbering family, although some distributor records list it under Siemens automation system compatibility. The 6ES7138-4CB11-0AB0 is a Siemens SIMATIC DP ET 200S power module, PM-E DC24 to 48 V or AC24 to 230 V, with diagnostics and a replaceable fuse.

Product Function and System Role

The 5136-DNS-200S acts as a DeviceNet scanner or master interface module that connects the controller rack or PLC system to a DeviceNet fieldbus network. It exchanges I/O data between the controller and DeviceNet-compliant sensors, actuators, drives, remote I/O blocks and other field devices. The 6ES7138-4CB11-0AB0 power module supplies and monitors the load voltage for ET 200S electronic modules in a voltage group, provides fuse protection and reports load voltage or fuse diagnostics to the DP master. The two components serve different system roles: the scanner handles network communication, while the power module handles local ET 200S supply voltage distribution and protection.

5136-DNS-200S Scanner Specifications

Distributor technical data for the 5136-DNS-200S lists a DeviceNet communication interface, single-slot interface module type, 24 V DC power supply and supported baud rates of 125 kbps, 250 kbps and 500 kbps. The module is designed for DeviceNet-compliant devices such as sensors, actuators and controllers on the fieldbus network. The scanner mounts in the controller rack or compatible PLC backplane and connects to the DeviceNet trunk or drop cable through the network connector. Exact backplane compatibility, memory, I/O capacity, connector pinout and diagnostic LED definitions should be verified from the original ProSoft or controller manufacturer scanner manual.

6ES7138-4CB11-0AB0 Power Module Specifications

The PM-E power module monitors the supply voltage for all electronic modules in its ET 200S voltage group. Supply voltage is fed in through the TM-P terminal module. The module can be assigned parameters for DC or AC load voltage and used with any compatible electronic module. It is required at least once for the ET 200S to the right of the interface module, except for the IM151-1 COMPACT design. The power module provides control interface PIQ and feedback interface PII in the process image for option handling, and its status is stored in the status byte in the process input image regardless of whether no-load voltage diagnosis is enabled.

Power Module Electrical Ratings

Rated load voltage for the PM-E module is 24 V DC to 56.7 V DC, or 24 V to 48 V, 120 V or 230 V AC. Maximum current-carrying capacity is 10 A. For 24 to 56.7 V DC, capacity is up to 10 A at up to 30 degrees Celsius, 9 A up to 40 degrees Celsius and 7 A up to 60 degrees Celsius. For 24 to 48, 120 or 230 V AC, capacity is up to 8 A at up to 30 degrees Celsius, 7 A up to 40 degrees Celsius and 5 A up to 60 degrees Celsius. No-load current from load voltage L1 or L+ is maximum 9 mA. Short-circuit protection uses a replaceable 5 by 20 mm fast fuse, IEC 127-2, 250 V, 10 A.

Terminal Assignment

PM-E terminals 2 and 6 are L+ or L1, and terminals 3 and 7 are M or N. L+ or L1 carries the rated load voltage of 24 V DC to 48 V DC; M is chassis ground and N is the neutral conductor. Terminals A4 and A8 are AUX1, a protective conductor terminal or potential bus freely usable up to 230 V AC. The module mounts on an ET 200S terminal module, and load voltage wiring follows the ET 200S power module and terminal module manual.

Power Module Diagnostics and LEDs

The PM-E module has a red SF batch error LED, green PWR load voltage LED and green FSG fuse LED. SF on with pending diagnosis indicates no parameter assignment or incorrect module plug-in; check parameter assignment and evaluate diagnostics. PWR off indicates no load voltage at the power module; check the load voltage. FSG off indicates the fuse has tripped; replace the fuse. Diagnostic messages include error 17D for encoder or load voltage missing when supply voltage is absent or too low, and error 18D for a defective fuse. If the fuse blows, only the affected power module diagnostic message is sent to the DP master, and the SF error LEDs of all modules in the voltage group light.

Power Module Parameters

Configurable PM-E parameters include no-load voltage diagnosis disabled or enabled, fuse blown diagnosis disabled or enabled, and voltage type DC or AC. Default settings are no-load voltage diagnosis disabled, fuse blown diagnosis disabled and voltage type DC. The 6ES7138-4CB11-0AB0 module is not a direct replacement for 6ES7138-4CB00-0AB0 in AC applications because supply voltage must be set to AC or DC. In DC applications, the new module acts as a direct replacement because the default parameter is DC; for AC replacement, a new hardware configuration must set the voltage type to AC.

Typical Application Scenarios

The 5136-DNS-200S scanner suits DeviceNet networks connecting remote I/O blocks, proximity sensors, photoeyes, valve manifolds, motor starters, drives, pneumatic modules or other DeviceNet field devices to a controller. The 6ES7138-4CB11-0AB0 power module suits ET 200S distributed I/O stations where electronic modules require a monitored and fused DC or AC load voltage group. Together, they may appear in a legacy PLC or distributed I/O assembly using DeviceNet communication and ET 200S powered I/O stations.

Installation and Configuration Notes

Installation must follow the scanner manual, ET 200S power module manual, local electrical codes and controller hardware configuration guidelines. For the scanner, verify backplane compatibility, DeviceNet baud rate, node address, cable length, terminator and device list. For the PM-E module, mount the module on the correct terminal module, wire L+ or L1, M or N and AUX1 according to the terminal assignment, select DC or AC voltage type in hardware configuration, enable diagnostics as required, and verify load voltage and fuse condition. Confirm total load current against the derating table and replace only with the specified 5 by 20 mm 10 A fast fuse.

Advantages and Selection Notes

The 5136-DNS-200S provides DeviceNet scanner communication at 125, 250 or 500 kbps with 24 V DC module supply for PLC fieldbus integration. The 6ES7138-4CB11-0AB0 provides ET 200S load voltage monitoring, DC or AC parameter selection, replaceable fuse protection, LED status indication and diagnostic messages to the DP master. When selecting replacements, confirm scanner controller compatibility, DeviceNet revision, baud rate and backplane slot; for the power module, confirm voltage type, current derating, terminal module, fuse rating and ET 200S station configuration. The scanner is a communication interface module, not an I/O module; the PM-E is a power distribution and protection module, not a communication module, CPU, sensor or contactor.