MEAN WELL TDR-960-24 RB73107838: 960W Three-Phase DIN Rail Power Supply Product Description

Brand and Product Identification

The MEAN WELL TDR-960-24, with reference number RB73107838, is a 960 W three-phase industrial DIN rail power supply from the Mean Well TDR-960 series. The TDR-960-24 model provides a 24 V DC output at 40 A rated current. The RB73107838 number is the unit or internal identification reference associated with this power supply. The TDR-960 series includes a 48 V DC version, TDR-960-48, rated 20 A and 960 W.

Product Function and System Role

The TDR-960-24 converts three-phase AC mains input into a regulated 24 V DC output for industrial control, automation, instrumentation and electrical panel loads. It supplies PLC systems, sensors, relays, actuators, communication equipment, drive control circuits and other 24 V DC loads in cabinets or machine control panels. The power supply includes active power factor correction, overload, overvoltage and overtemperature protection, DC OK status signaling and current-sharing support for parallel redundant or higher-power configurations.

Input Specifications

The power supply accepts a three-phase input voltage range of 340 to 550 V AC, with dual-phase operation allowed under specified derating. It also supports a DC input range of 480 to 780 V DC. Input frequency range is 47 to 63 Hz. Typical power factor is 0.88 or higher at 400 VAC and 0.86 or higher at 500 VAC at full load. Typical AC current is 2 A at 400 VAC or 1.4 A at 500 VAC. Typical inrush current at cold start is 60 A, and leakage current is below 3.5 mA at 530 VAC.

Output Specifications

The TDR-960-24 output is 24 V DC, with rated current 40 A and current range 0 to 40 A. Rated power is 960 W. Maximum ripple and noise is 180 mV peak to peak. Output voltage adjustment range is 24 to 28 V. Voltage tolerance is plus or minus 1.0 percent, line regulation is plus or minus 0.5 percent and load regulation is plus or minus 1.0 percent. Setup time is 1000 ms at 400 VAC or 800 ms at 500 VAC, rise time is 100 ms, and typical hold-up time is 12 ms at 400 VAC or 14 ms at 500 VAC at full load.

Protection and Functions

The TDR-960-24 provides short circuit, overload, overvoltage and overtemperature protection. Overload protection operates at 105 to 130 percent of rated output power, using constant current limiting; the unit shuts down after 3 seconds and recovers when repowered. Overvoltage protection trips at 29 to 33 V and shuts down the output, recovering on repower. Overtemperature protection shuts down the output and recovers automatically after temperature decreases. A built-in DC OK relay contact closes when the power supply turns on and DC output is normal, and opens when the supply turns off or DC fails. Relay contact rating is 60 V DC at 0.3 A, 30 V DC at 1 A or 30 V AC at 0.5 A resistive load.

Parallel Operation and Current Sharing

Parallel operation is supported through P plus and P minus current-sharing connections. Output voltage differences between parallel units should be below 0.2 V. Total output current must not exceed rated current per unit times number of units times 0.9. Up to four units may be paralleled according to the function manual. Parallel wiring should use short, large-diameter cables connected to the load, and minimum load should exceed 5 percent of total rated current per unit. Under light load in parallel mode, the master unit may operate while slave units remain in standby, which affects their output LEDs and relays.

Mechanical Construction and Installation

The TDR-960-24 measures 110 mm width, 125.2 mm height and 150 mm depth, with a mass of approximately 2.47 kg. It mounts on a TS 35/7.5 or TS 35/15 DIN rail. Input terminal TB1 assigns pin 1 to FG, pin 2 to AC L3, pin 3 to AC L2 and pin 4 to AC L1. Output terminal TB2 assigns pins 1, 2 and 3 to positive DC output and pins 4, 5 and 6 to negative DC output. The control connector assigns pins 1 and 2 to current share and pins 3 and 4 to DC OK relay contact. Recommended clearance is 40 mm above, 20 mm below and 5 mm on each side under full-load permanent operation, with 15 mm side clearance adjacent to a heat source.

Environmental and Safety Ratings

Operating temperature ranges from minus 30 to plus 70 degrees Celsius, subject to derating. Operating humidity is 20 to 95 percent relative humidity, non-condensing. Storage temperature ranges from minus 40 to plus 85 degrees Celsius. Temperature coefficient is plus or minus 0.03 percent per degree Celsius between 0 and 50 degrees Celsius. The supply complies with UL 508 industrial control equipment, AS/NZS 62368.1, IEC 62368-1 CB scheme, and applicable EMC emission and immunity standards. Withstand voltage is 3 kV AC input to output, 2 kV AC input to frame ground, and 0.5 kV AC output to frame ground.

Typical Application Scenarios

Typical applications include three-phase industrial control panels, PLC and automation system power supplies, machine tool and production line DC power, sensor and actuator supply, communication and monitoring equipment, material handling and packaging machinery, process control cabinets and distributed control systems requiring a 24 V DC DIN rail supply. The parallel and DC OK functions suit redundant or high-current 24 V systems where status monitoring and load sharing are required.

Advantages and Selection Notes

The TDR-960-24 offers 960 W output in a 110 mm wide DIN rail package, three-phase 340 to 550 V AC input, active PFC, 94 percent typical efficiency, convection cooling, built-in protections, DC OK relay, current sharing and a three-year warranty. When selecting a replacement, confirm output voltage, rated current, input phase and voltage, DIN rail size, parallel requirement and cabinet clearance. The power supply is an AC-DC DC source, not a battery charger, UPS, inverter, servo drive, controller or field sensor; its role is to convert three-phase mains power into regulated 24 V DC for industrial control loads.