Description

MITSUBISHI ELECTRIC FX2N-232IF 1580219: MELSEC-F RS232C Interface Block Product Description

Brand and Product Identification

The MITSUBISHI ELECTRIC FX2N-232IF, associated with serial or production number 1580219, is an RS232C special function interface block for the Mitsubishi MELSEC-F FX series programmable controllers. The model FX2N-232IF identifies the RS232C communication block, and the number 1580219 corresponds to the unit identification or production number on the individual module. The 232IF block connects to FX2N, FX2NC, FX3U and FX3UC series PLCs to provide full-duplex serial data communication with another RS232C device such as a personal computer, barcode reader, printer or serial instrument.

Product Function and System Role

The FX2N-232IF expands a Mitsubishi FX PLC with one RS232C communication channel. It performs full-duplex asynchronous serial communication without requiring a dedicated protocol. Communication parameters and data are handled through buffer memory, abbreviated BFM, using the FROM and TO PLC instructions. The module allows the PLC to exchange serial data with external RS232C equipment, supporting applications such as serial data acquisition, printer output, barcode reader input, HLS or instrument communication, and legacy device integration within an FX control system.

Communication Specifications

The interface conforms to the RS232C transmission standard. Maximum transmission distance is 15 m, and the connection is one-to-one, 1:1. Supported baud rates are 300, 600, 1200, 2400, 4800, 9600 and 19200 bps. Communication method is no-protocol full-duplex asynchronous communication. The send and receive buffer accommodates 512 bytes or 256 words. In RS232C interlink connection mode, data exceeding the 512 byte or 256 word buffer can also be received. The module also provides ASCII to HEX and HEX to ASCII conversion for numeric data handling.

Connector and Signal Layout

The FX2N-232IF uses a 9-pin D-SUB connector with number 4-40 UNC inch screw thread. The pin assignment is pin 1 CD or DCD carrier detection, pin 2 RD or RXD receive data, pin 3 SD or TXD send data, pin 4 ER or DTR data terminal ready, pin 5 SG signal ground, pin 6 DR or DSR data set ready, pin 7 RS or RTS request to send, pin 8 CS or CTS clear to send, and pin 9 CI or RI calling indication. Some handshake signals indicate status only, while RTS and CTS follow the configured send or receive enable state.

Power Supply and Occupied I/O

The module draws 5 V DC at 40 mA from the programmable controller internal power supply. It also requires an external 24 V DC supply within plus or minus 10 percent at 80 mA. The POWER LED lights when both the 5 V DC supply from the main unit and the 24 V DC external terminal supply are present. The interface block occupies 8 I/O points taken from the PLC extension bus, which may be configured as input or output points.

Isolation and Electrical Ratings

The FX2N-232IF provides photocoupler isolation between the PLC communication side and the RS232C external interface. Withstand voltage is 500 V AC for one minute between the entire external terminal and the ground terminal. General specifications excluding withstand voltage match those of the main PLC unit. The isolated serial interface helps reduce ground-loop and noise effects between the PLC and externally connected RS232C equipment.

Mechanical Construction and Mounting

The module dimensions are approximately 55 mm wide, 85 mm deep and 80 to 90 mm high according to the hardware manual, with a weight of approximately 0.3 kg. It mounts on a 35 mm DIN rail using the DIN rail clip and DIN rail groove, or through two mounting holes of 4.5 mm diameter. The module connects to the PLC through the extension cable and next-step extension connector, allowing additional special function blocks to be connected in the expansion stack. Accessories include a special block number label.

LED Indicators and Diagnostics

The FX2N-232IF provides three LEDs. The POWER LED indicates that PLC 5 V DC power and external 24 V DC power are supplied. The SD LED lights while data is being sent to the connected RS232C equipment. The RD LED lights while data is being received from the connected RS232C equipment. These indicators support basic commissioning, cable checking and communication fault diagnosis.

Applicable PLC System Configuration

The interface block is applicable to FX2N, FX2NC, FX3U and FX3UC series programmable controllers. Up to eight special function blocks can be connected to FX2N, FX3U and FX3UC PLCs, with up to seven on the FX3UC-32MT-LT(-2) model. Up to four special function blocks can be connected to an FX2NC PLC. The PLC program accesses the module through FROM and TO instructions and configures communication via buffer memory settings.

Typical Application Scenarios

Typical FX2N-232IF applications include connecting an FX PLC to a serial personal computer, barcode reader, label printer, weighing instrument, serial display, sensor controller or legacy RS232C device. It suits non-protocol full-duplex data exchange where the PLC reads or writes serial messages to external equipment. Common industries include packaging, material handling, machine tools, assembly automation, textile, printing, food processing and retrofit installations based on Mitsubishi FX controllers.

Installation and Commissioning Notes

Installation and programming should follow the Mitsubishi FX2N-232IF hardware manual and the applicable FX PLC programming manual. Mount the block on the DIN rail or panel, connect the extension cable to the PLC, wire the external 24 V DC supply, and connect the RS232C device to the 9-pin D-SUB connector. Verify baud rate, data format, buffer memory assignment, handshake configuration and communication program before testing. Check POWER, SD and RD LEDs during serial communication. If replacing an existing module, confirm the PLC series, occupied I/O assignment, buffer program and cable pinout match the original installation.

Advantages and Selection Notes

The FX2N-232IF offers one isolated RS232C channel, full-duplex asynchronous communication, non-protocol operation, 512 byte or 256 word buffer, ASCII HEX conversion, DIN-rail mounting, LED status indication and compatibility with FX2N, FX2NC, FX3U and FX3UC controllers. Note that this is a discontinued MELSEC-F special block according to Mitsubishi product status, with end-of-order information recorded for the series. When selecting a replacement, confirm whether the application requires RS232C, RS485, RS422 or USB communication, and verify compatibility with the existing PLC model and program. The FX2N-232IF is a communication interface block, not a CPU, power supply, digital I/O module, field sensor or serial printer; its role is to provide an isolated RS232C serial port for PLC data exchange.


Get a Quote