Description

EATON NZM1 + LZM1 80-100: NZM1 Frame LZM1 Molded Case Circuit Breaker Product Description

Brand and Product Identification

The EATON NZM1 + LZM1 80-100 refers to an Eaton Moeller series molded case circuit breaker assembled on the NZM1 frame, using the LZM1 circuit-breaker family with a rated current range of 80 to 100 A. In Eaton's naming convention, NZM1 defines the frame size and mechanical platform, while LZM1 identifies the breaker type within the same frame class. The 80-100 designation indicates that this frame covers 80 A and 100 A rated current settings. The LZM and NZM ranges share equal dimensions and modular accessory mounting, so an LZM1 breaker fits the same NZM1 frame installation arrangement and uses compatible NZM1 accessories such as rotary handles, shunt releases, undervoltage releases and auxiliary contacts.

Product Function and Protection Purpose

The LZM1 molded case circuit breaker provides overload and short-circuit protection for low-voltage distribution systems, cables, conductors and connected loads. It switches and protects electrical circuits in residential, commercial and industrial buildings, panelboards, machine controls, motor starter combinations and power distribution boards. The breaker carries the load current under normal operating conditions and trips automatically when an overload or short-circuit current exceeds the set protection threshold, thereby limiting conductor heating and protecting downstream equipment.

Trip Unit and Current Settings

The standard LZM1 breaker uses a thermomagnetic release. The overload release Ir is adjustable from 0.8 to 1 times the rated current In, with the factory setting typically at 0.8 times In. The short-circuit release Ii provides instantaneous tripping with an adjustable threshold in the range of 6 to 10 times In for frame 1 devices. For neutral-pole protection on four-pole versions, the neutral pole is protected by the thermal device with a tripping threshold of 100 percent or 60 percent of the phase Ir threshold. Electronic release versions are also available in the broader LZM range, but the standard LZM1 80-100 configuration described here follows the thermomagnetic A-release arrangement.

Electrical Ratings and Breaking Capacity

The LZM1 breaker belongs to a four-frame-size LZM series covering rated currents up to 1000 A. Frame 1 devices cover ratings in the low-current range, including 63 A, 80 A, 100 A, 125 A and 160 A in the technical data tables, with the 80-100 designation matching the 80 A and 100 A settings within this frame. LZM1 models are offered in different breaking capacity levels, identified by the series prefix such as LZMB1 for basic capacity, LZMC1 for comfort capacity and LZMN1 for normal or current-limiting capacity. Rated operational voltage extends up to 690 V AC according to the LZM catalog, while short-circuit breaking capacity values are expressed at 400/415 V and 440 V and vary by breaking capacity class. The actual Icu, Ue and pole count for a specific unit must be checked against its Eaton catalog number or product nameplate, because breaking capacity and release type differ between LZMB1, LZMC1 and LZMN1 variants.

Standards and Certification

The LZM and NZM circuit breakers are designed to IEC/EN 60947-2 and are suitable for worldwide use, with applicable IEC, UL/CSA and CCC certification depending on the specific model and market. They provide direct-contact protection that is finger and back-of-hand proof to the relevant VDE standard, and they meet climatic proofing requirements for damp heat conditions. The breaker has main switch characteristics for machine applications according to IEC/EN 60204 and isolating characteristics according to IEC/EN 60947.

Mechanical Construction and Mounting

The LZM1 housing is a compact molded case breaker body matching the NZM1 frame dimensions. The breaker supports modular function groups and flexible mounting arrangements, including fixed mounting and door-coupled rotary handle options through NZM1 accessories. Plug-in or withdrawable arrangements and busbar or cable terminal configurations depend on the selected accessory package. The front installation position allows auxiliary contacts and release modules to be clipped on without disassembling the breaker body, reducing mounting time and reducing the number of spare parts required.

Typical Application Scenarios

Typical NZM1 plus LZM1 80-100 applications include main feeders and branch feeders in distribution boards, protection of power cables and busbar taps, machine and panelboard incoming protection, lighting and socket distribution, motor feeder protection where the breaker characteristics match the motor starting current, and industrial control panel protection. The frame is suited to installations where the load current falls in the 80 to 100 A range and where coordination with upstream or downstream breakers is planned for selectivity.

Installation, Coordination and Maintenance Notes

Installation and commissioning should follow the Eaton LZM/NZM instruction leaflet, local electrical codes and the rated current, voltage and breaking capacity selected for the circuit. The panel builder remains responsible for temperature rise calculation, short-circuit rating verification and coordination of the breaker with cables, busbars and upstream protective devices. Heat dissipation data provided by Eaton should be used in enclosure thermal design. Maintenance consists of periodic inspection of connections, operating mechanism, auxiliary contacts and trip unit condition, and verification that the breaker trips correctly under test conditions. If an undervoltage release, shunt release, auxiliary contact or remote operator is fitted, the accessory must match the NZM1/LZM1 platform and its control voltage must match the system supply.

Advantages and Selection Notes

The NZM1 plus LZM1 80-100 combination offers a compact frame, adjustable overload and short-circuit releases, shared NZM1 accessory compatibility, worldwide standards coverage and a choice of breaking capacity levels. When ordering or replacing a unit, the user should confirm the exact model code, pole count, rated current, release type, breaking capacity class, accessories and control voltage. The LZM1 is a molded case circuit breaker for protection and switching, not a contactor, motor starter, soft starter or isolator-only switch-disconnector; its role is to protect and interrupt low-voltage distribution circuits under normal and fault conditions.