FOXBORO P0916PH I/A Series 16-Channel HART Analog Input Termination Module
June 11, 2026

FOXBORO P0916PH I/A Series 16-Channel HART Analog Input Termination Module

FOXBORO P0916PH is a dedicated termination assembly matching I/A Series DCS analog input modules, specially optimized for HART protocol intelligent transmitters. It supports 16 single-ended / 8 differential analog signal channels, compatible with standard 4-20mA, 1-5V field sensor signals, and realizes bidirectional HART digital communication with field instruments to access remote calibration, parameter reading and fault diagnosis data. Built-in full-channel optoelectronic isolation (2500VAC isolation withstand voltage), independent surge suppression and signal filtering circuits effectively resist industrial EMI interference. Adopts compact DIN rail pluggable structure, equipped with standard DB25 backplane interface and field terminal wiring block, seamlessly docked with FBM analog input modules. With high measurement accuracy up to ±0.02%FS, 16-bit high resolution and 100Hz fast sampling rate, it delivers stable, high-precision signal acquisition for continuous process industries, adapting to high humidity, corrosive G3 industrial environments.

Description

FOXBORO P0916PH Operation Specification Manual

1. Basic Product Information

Model: P0916PH
Brand: FOXBORO (Schneider Electric Foxboro)
Product Type: HART Analog Input Termination Module
Applicable System: I/A Series Distributed Control System
Rated Supply Voltage: 24VDC
Typical Power Consumption: ≤12W
Overall Dimension: 88.9mm × 31.75mm × 101.6mm
Net Weight: 0.42kg
Protection Grade: IP20 cabinet internal use
Mounting Method: Standard DIN rail rack mounting
Interface: DB25 backplane bus connector + screw terminal block for field wiring

2. Core Signal Technical Parameters

  1. Channel Configuration

  • Max 16 single-ended analog input channels or 8 differential input channels (software configurable)

  • Supported input signals: 4–20mA DC, 0–20mA DC, 1–5VDC, 0–5VDC

  • HART Function: Support HART 5/7 bidirectional communication for intelligent transmitters

  1. Measurement Performance

  • Basic Accuracy: ±0.02% Full Scale

  • Resolution: 16-bit high precision ADC

  • Sampling Rate: 100Hz per independent channel

  • Input Impedance: ≥10MΩ (voltage signal); ≤10Ω (current signal)

  1. Isolation & Protection

  • Channel-to-backplane optocoupler isolation, isolation voltage ≥2500VAC

  • Built-in TVS surge protection, short-circuit self-recovery protection per channel

  • EMI/RFI filtering circuit to suppress motor, frequency converter interference

3. Environmental Operating Specifications

Operating Temperature Range: -10℃ ~ +65℃
Storage Temperature Range: -40℃ ~ +85℃
Relative Humidity: 5%~95% RH, non-condensing
Corrosion Grade: IEC G3, resistant to industrial oil mist, weak acid/alkali gas
Vibration Standard: Comply with IEC 60068 industrial vibration test standard

4. Installation & Operating Instructions

  1. Mounting Steps

    (1) Fix standard 35mm DIN rail inside DCS control cabinet

    (2) Snap P0916PH module onto DIN rail and lock the bottom buckle

    (3) Connect DB25 cable between module backplane port and FBM analog input module

  2. Field Wiring Rules

  • Field transmitter cable: Shielded twisted pair wire, single channel independent wiring

  • HART signal wiring: Keep cable length ≤500m, avoid parallel laying with high-power power lines

  • 24VDC power wiring: Distinguish positive and negative poles, ground shielding layer at single end of cabinet

  1. System Startup & Configuration

    (1) Confirm all wiring is completed, close cabinet door and switch on 24VDC power supply

    (2) The module self-tests within 30 seconds; steady green indicator = normal, flashing red = channel fault

    (3) Log in I/A Series workstation, configure channel mode (single-ended/differential), signal type and HART communication switch

    (4) Download configuration parameters to module, read real-time sensor data and HART instrument information

  2. Routine Maintenance

  • Inspect indicator lights and terminal wiring tightness per shift

  • Clean dust on wiring terminals every month to prevent poor contact

  • Execute HART instrument remote parameter calibration every quarter

5. Safety Precautions

  1. Do not plug/unplug DB25 communication cable or field signal wires with power on; cut off 24VDC power before wiring maintenance to avoid module circuit burnout.

  2. Keep the module away from high-temperature heat sources, liquid splashing and strong electromagnetic equipment.

  3. Do not disassemble the internal circuit board without authorization; maintenance shall be operated by Foxboro certified automation technicians only.

  4. If continuous red fault alarm occurs, cut off power immediately to check short circuit, open circuit or overload of field transmitter loops.

6. Fault Diagnosis & Troubleshooting

  1. All indicator lights off: Check cabinet 24VDC power supply circuit and loose power terminals

  2. Single channel red fault light: Inspect field transmitter open circuit, short circuit or wiring disconnection

  3. HART communication failure: Check shielded cable laying distance, terminal contact and HART protocol parameter matching

  4. Signal data fluctuation abnormally: Increase signal filtering parameter, reprocess cable shielding grounding

4. Application Fields (English Version)

  1. Petrochemical Industry: Refinery, ethylene plant, reactor temperature/pressure/flow HART transmitter signal collection

  2. Oil & Gas Industry: Onshore oil extraction, natural gas pipeline, LNG tank level and pressure monitoring

  3. Thermal Power Industry: Boiler flue gas analysis, water supply system, steam turbine auxiliary analog signal acquisition

  4. Metallurgical Industry: Smelting furnace temperature thermocouple, rolling mill pressure transmitter HART signal processing

  5. Water Treatment Industry: Sewage PH, dissolved oxygen, flow intelligent transmitter real-time data collection

  6. Pulp & Paper Industry: Cooking tank pressure, paper machine slurry flow precise analog signal measurement

  7. Fine Chemical & Pharmaceutical Industry: Fermentation tank temperature, pressure, liquid level high-precision HART signal monitoring

  8. Cement & Building Materials Industry: Rotary kiln temperature, raw material silo level sensor signal acquisition

Supplementary Remarks

All English texts adopt international industrial automation standard terminology, suitable for foreign trade product detail pages, PDF specification sheets, engineering bidding documents and customs declaration materials. All technical parameters conform to official Foxboro I/A Series P0916PH termination module factory standards.


Get a Quote