FOXBORO P0916KN RTD Compression Termination Assembly for I/A Series FBM203 DCS Module
Description
FOXBORO P0916KN Operation & Specification Manual
1. Basic Product Information
Brand: FOXBORO (Schneider Electric Process Automation, former Invensys)
Model: P0916KN
Product Category: RTD Resistance Temperature Detector Compression Termination Assembly (TA)
Matching DCS Platform: I/A Series Distributed Control System
Compatible FBM Module: FBM203 (8-channel isolated RTD input module)
Certifications: CE, UL, ISO9001
Mounting Method: Standard 35mm DIN rail installation inside control cabinet
Protection Class: IP20 (indoor cabinet use only)
Overall Dimension: 135mm × 162mm × 43mm
Net Weight: Approx. 290g
MTBF: ≥55,000 working hours
2. Electrical Technical Parameters
Auxiliary Power Supply: DC 24V, power consumption ≤7.8W
Signal Channel Quantity: 8 independent fully isolated RTD input channels
Supported RTD Sensors: PT100, PT1000, Cu50, Ni100 (2-wire / 3-wire / 4-wire connection compatible)
Temperature Measurement Precision: ±0.08℃ within -200℃ ~ +600℃ measuring range
Built-in Excitation Circuit: Stable constant current excitation per channel, low self-heating error
Channel Isolation Strength: 1500Vrms AC isolation between each channel and ground
Compression Terminal Wiring Spec: Applicable wire 0.2–4mm² solid/stranded wire, 24–12AWG ferrule wire
Built-in Protection Circuit: Reverse connection prevention, channel surge absorption filter, overvoltage & short-circuit suppression
Matching Connection Cable: 37-pin shielded special cable, optional length 0.5m–30m, LSZH low-smoke halogen-free cable optional
Redundancy Compatibility: Supports dual FBM203 redundant hot standby, zero signal interruption during module fault switching
3. Environmental Operating Conditions
Continuous Operating Temperature: 0℃ ~ +60℃ (ventilated sealed control cabinet)
Storage & Transportation Temperature: -40℃ ~ +85℃
Relative Humidity: 5%–95% RH, non-condensing
Anti-Interference Standard: Complies with IEC G3 industrial vibration and EMI standards, adapts to high-dust, high-frequency inverter interference workshop environment
4. Installation & Operating Procedures
Snap P0916KN onto 35mm DIN rail in control cabinet, lock the side fixing buckle tightly to avoid loose contact.
Connect the matched 37-pin shielded cable between the termination assembly and FBM203 baseplate connector.
Wire on-site RTD thermal resistance probes to compression terminals by channel serial number; strictly separate RTD compensation wires from high-power power cables.
Switch on DC24V auxiliary power, confirm the green power indicator remains steady on.
Complete RTD sensor type selection, wire mode setting and channel address mapping via Foxboro Evo configuration software.
Maintenance Operation: Matched FBM203 modules support hot swap; faulty modules can be replaced directly without stopping the whole production control system.
Fault Indication Definition: Red flashing LED = channel short circuit / open circuit / signal drift; yellow steady LED = redundant channel normal standby state.
5. Safety & Maintenance Precautions
Only certified professional industrial automation technicians are allowed to disassemble, wire and debug this termination assembly.
Fully cut off DC24V power supply before field wiring to prevent channel burnout and permanent temperature measurement deviation.
Clean terminal block dust and metal oxide every 3 months to avoid temperature signal drift caused by poor contact.
Store spare P0916KN units in dry, ventilated warehouse; avoid long-term exposure to corrosive gas, oil mist and damp environment.
Standard Warranty Period: 12 months under rated normal industrial operating environment.
4. Application Fields
Oil & Gas Industry
Refinery pipeline medium temperature monitoring, storage tank PT100 temperature signal collection, crude oil heating furnace low-medium temperature precise measurement wiring.
Thermal Power & New Energy Power Plants
Boiler water wall, condenser, turbine auxiliary pipeline RTD temperature acquisition; wind generator bearing temperature real-time monitoring; photovoltaic heat storage system temperature signal transmission.
Chemical & Pharmaceutical Factories
Chemical reactor, distillation tower medium temperature closed-loop control; pharmaceutical fermentation tank, drying oven high-precision temperature monitoring; low-temperature reaction workshop RTD signal isolation transmission.
Pulp & Paper Industry
Paper pulp cooking tank, drying roller medium temperature continuous measurement; papermaking workshop heat exchange equipment temperature parameter collection.
Food & Beverage Industry
Food sterilization tank, baking tunnel, beverage fermentation tank constant temperature monitoring and signal conversion.
Metallurgy & Mining
Sintering machine cooling section temperature monitoring, mineral processing heating equipment RTD signal docking.
Municipal & Environmental Protection
Waste water treatment tank medium temperature collection, waste incineration flue cooling section temperature monitoring, central air conditioning system PT100 sensor signal access.
Information Certainty Explanation
Confirmed content: P0916KN is Foxboro I/A Series RTD compression termination assembly, matching FBM203, 8 isolated channels, compatible PT100/PT1000 multi-wire RTD, DC24V power supply, 1500Vrms channel isolation, DIN rail installation, CE/UL certification, built-in constant current excitation & multi-layer protection, standard seven major temperature monitoring industries, wiring range and environmental temperature range are consistent with official I/A series TA hardware specifications.
Content to be verified: Complete matched cable part number list, full factory original temperature calibration test report, detailed 2/3/4-wire RTD parameter configuration steps need to refer to Foxboro official FBM203 PSS technical manual for further confirmation.
Get a Quote