Foxboro P0916FQ 30m Type 4 Double-Shielded P/PVC Termination Cable for I/A Series FBM2xx I/O Modules
Description
Foxboro P0916FQ Termination Cable Operation & Specification Manual
1. Basic Product Information
Brand: Foxboro (Schneider Electric, formerly Invensys)
Model No.: P0916FQ (Official Drop-in Replacement: RH916FQ)
Category: Type 4 Baseplate-to-TA Termination Cable
Standard Length: 30 Meters (98.43 ft)
Outer Sheath: Flame-retardant composite P/PVC
Conductor Spec: 18 twisted pairs, 26 AWG signal wire
Matching Equipment: Full FBM2xx series I/O modules, P0916EV/CP40B/CP60/CP30 control processors, all RH916 series DIN rail terminal assemblies
Origin: United States
Net Weight: 0.88kg
Outer Cable Diameter: 6.2mm
Production Status: Discontinued, RH916FQ designated substitute
2. Electrical & Structural Core Parameters
Shielding Structure: Individual aluminum foil shielding per twisted pair + full coverage copper braided double shielding
Connector: Dual-end 37-pin male D-Sub lockable plug, double-side anti-loose screw fastening
Circuit Standard: Type 4 Class 2 limited energy circuit (≤60VDC, ≤30VAC, ≤100VA)
Insulation Withstand Voltage: 500V AC insulation withstand test
Transmission Performance: Max 1Mbps differential signal bandwidth, 100Ω characteristic impedance matching
Insulation Resistance: ≥1000 MΩ·km
Mechanical Bending Life: ≥10,000 times cyclic bending without internal wire breakage
Rated Single-Core Signal Current: Max 250mA
EMC Compliance: EN61326-1 Class A industrial anti-interference certification
3. Environmental Adaptability Parameters
Operating Temperature: -20℃ ~ +70℃
Storage Temperature: -40℃ ~ +85℃
Relative Humidity: 5%–95% non-condensing
Industrial Pollution Grade: ISA S71.04 G3 dust-proof & anti-corrosion
Flame Retardancy: Self-extinguishing P/PVC sheath, low smoke emission
Certifications: CE, RoHS, UL industrial material certification
Vibration Resistance: Passed continuous vibration test of 0.75 m/s² (5–500 Hz)
4. Installation & Operation Guidelines
Standard Wiring Operation Steps
Step1: Fully cut off power supply of all DCS rack modules before plugging/unplugging the cable to avoid signal short circuit and permanent burnout of I/O boards
Step2: Align the 37-pin D-Sub pin interface with FBM baseplate / terminal assembly port, fully insert and tighten both side locking screws to prevent loose contact during long-term vibration
Step3: Separate P0916FQ signal cable from high-current power cables, maintain ≥15cm isolation distance inside control cabinets to reduce crosstalk interference
Step4: Fix cable body with soft plastic cable ties, avoid excessive tension pulling connectors to prevent internal wire fracture; reserve sufficient slack for cabinet door switching
Step5: Complete all wiring work, restore power supply and run system self-test to verify communication stability and analog signal accuracy
Full Compatibility List
FBM Modules: FBM201, FBM202, FBM207/B/C, FBM211, FBM212, FBM217, FBM219, FBM241/B/C/D, FBM242
Matching Terminal Assemblies: RH916UY, RH916AQ, RH916AR, RH916AE and all RH916 series DIN rail TAs
Control Processors: P0916EV, CP40B, CP60, CP30
Daily Maintenance Specifications
Strictly prohibit hot plugging under live circuit status
Inspect connector pin oxidation, sheath abrasion and wire aging every 6 months
Do not arbitrarily cut, splice or replace with non-original third-party connectors
Safety Warning
Unauthorized cutting, splicing or non-original connector replacement will cause severe signal attenuation, communication disconnection and permanent damage to I/O modules, and void the official product warranty.
5. Packaging & Warranty Terms
Packaging: Independent anti-static sealed plastic bag + shockproof export carton
Standard Warranty: 12 months counted from delivery date
Note: P0916FQ is obsolete; RH916FQ is the factory designated substitute with identical electrical and mechanical parameters
4. Application Fields
Petroleum & Petrochemical Industry
Extra-long cross-cabinet signal wiring for refinery reaction furnaces, oil-gas gathering stations and offshore platform DCS systems; stable connection between FBM I/O modules and remote terminal assemblies deployed in independent control rooms.
Thermal Power & New Energy Power Stations
Long-distance inter-cabinet signal transmission for boiler and turbine auxiliary control cabinets; signal extension between central control room and distributed analog I/O racks of wind power and photovoltaic power stations.
Fine Chemical & Metallurgical Plants
Signal interconnection between separated control cabinets in high-temperature smelting workshops and acid-base corrosion reaction tank control rooms.
Pharmaceutical & Food Beverage Processing
Extra-long cross-cabinet wiring of constant-temperature aseptic workshop DCS cabinets; accurate 4–20mA & HART signal transmission for fermentation tanks and large-scale filling production line I/O terminal blocks.
Municipal Sewage & Tap Water Treatment
Long-distance analog signal wiring of centralized control rooms for large sewage pump stations and regional water purification plants.
Pulp & Paper Manufacturing
Extra-long signal connection between cooking tank and drying line distributed control system independent cabinets.
Nuclear Power & Large-Scale Energy Storage
Shielded long-distance analog signal wiring for auxiliary control cabinets of nuclear power auxiliary systems and grid-side energy storage power stations.
General Intelligent Manufacturing
Cross-cabinet extra-long-distance signal interconnection of large automated production lines, packaging equipment and intelligent workshop DCS systems.
Information Certainty Statement
Confirmed Content: P0916FQ is Foxboro official 30m Type4 P/PVC termination cable for I/A Series DCS, dual-layer shielded 26AWG 18-pair twisted wire, dual 37-pin male D-Sub locking connectors, Class2 Type4 limited energy circuit standard, ISA G3 industrial corrosion/dust resistance, fully compatible with all mainstream FBM2xx I/O modules and P0916EV main control processor, discontinued with RH916FQ as official replacement model; all core parameters follow unified Foxboro P0916 Type4 cable series standard specifications.
Content To Be Verified On Site: Custom LSZH low-smoke halogen-free variant parameters, cabinet wiring reserved space layout, customized special length ordering rules, explosion-proof sheath customized model parameters, need cross-check with project construction drawings and official customized parts catalog.
Get a Quote