Foxboro P0916AG 24VDC Output Redundant Power Module with 18–36VDC Wide DC Input for I/A Series DCS Distributed Control System
Description
3. Product Specification Manual
3.1 Basic Parameters
Part Number: P0916AG
Product Type: DC-DC Rack Redundant Power Supply Unit
Manufacturer: Foxboro (AVEVA / Schneider Electric)
Applicable System: I/A Series DCS Distributed Control System
Core Function: Wide-range DC-DC conversion, stable 24VDC rack power supply, dual hot standby redundant backup for DC-powered control cabinets
DC Input Range: 18VDC ~ 36VDC wide field DC bus
Rated Regulated Output: 24VDC DC
Max Output Power: 250W
Protection Class: IP20
Housing Material: Die-cast aluminum alloy integrated heat sink
Net Weight: 0.48kg
Installation Mode: Vertical slot mounting inside standard 19-inch industrial control cabinet
Compatible Hardware: Full P0914 series backplanes, P0914WP controllers, P0914YM/YZ FCM communication modules, all FBM analog/digital I/O modules, P0915DX/FB/FC terminal bases
3.2 Electrical Performance
Output Voltage Regulation Precision: ±0.5% stability under full load fluctuation
Output Ripple & Noise: ≤130mV peak-to-peak
Redundancy Working Mode: Dual-module parallel hot standby with automatic average current sharing
Fault Switch Characteristic: Instant non-interrupt transfer without output voltage sag during single module breakdown
Input Filter Design: Multi-level differential LC filter to suppress DC bus spike and EMI interference
Cooling Method: Fanless natural passive convection heat dissipation, maintenance-free long-term operation
3.3 Maintenance & Diagnostic Functions
Hot Swap Support: Online plug-and-play replacement without disconnecting cabinet DC input power
On-board Real-time Self-Diagnosis: Detect DC input loss, input undervoltage/overvoltage, output overload, short-circuit, internal over-temperature and hardware damage
LED Status Definition: Steady green = normal stable output; flashing red = power system fault alarm
Redundancy Configuration: Direct parallel installation without additional configuration software
Load Adaptability: Stable drive for mixed loads of communication, temperature, HART and digital switching I/O modules
3.4 Environmental Technical Index
Operating Temperature Range: 0℃ ~ +60℃
Storage Temperature Range: -40℃ ~ +85℃
Relative Humidity: 5% ~ 95% non-condensing
Dust Resistance Standard: ISA S71.04 Class G3 industrial dust environment compliance
Vibration Resistance: Pass IEC60068 industrial anti-vibration durability test
Industrial Certifications: CE, UL global industrial safety certification
3.5 Full Built-in Safety Protection Circuits
Input undervoltage/overvoltage lockout protection: Automatically stop output when DC bus exceeds 18–36V range to protect downstream DCS hardware
Output overvoltage protection: Instant cut-off of 24VDC output when abnormal high voltage occurs
Overcurrent & short-circuit self-limiting protection: Fast current limiting shutdown for shorted field loops
Over-temperature protection: Progressive power derating followed by full shutdown at critical temperature
Reverse DC input polarity protection to avoid module burnout from reversed field power wiring
Input transient surge absorption circuit to resist DC bus switching voltage spikes
3.6 Step-by-Step Installation Instructions
Vertically insert P0916AG DC power module into dedicated power slot of P0914 series rack backplane in standard 19-inch cabinet;
Connect 18–36VDC field DC bus cable to rear input terminal block, strictly distinguish positive and negative poles and fasten terminals tightly;
For redundant power architecture: Install two P0916AG modules in adjacent power slots to realize automatic load-sharing backup;
Confirm all controllers, communication cards and FBM I/O modules are fully locked into backplane slots;
Switch on field DC input power, observe front LED: steady green light means stable 24VDC power supply for the entire rack;
Maintenance operation: Hot-swap faulty P0916AG directly without cutting off cabinet DC power; standby unit continuously supplies power to avoid DCS system interruption.
4. Application Fields
Offshore oil platforms, remote natural gas compressor stations (24V DC battery bus power supply)
New energy wind turbine, photovoltaic power station remote DCS control cabinets
Hydropower station on-site local control rooms powered by station DC battery pack
Long-distance pipeline unattended monitoring substation control cabinets
Mining underground auxiliary monitoring and interlock control racks with DC battery power
Remote municipal sewage pump stations and rural water supply unattended control cabinets
Transport chemical tank terminals, remote loading station DCS monitoring racks
Outdoor industrial park distributed HVAC and heat exchange DC control cabinets
Information Verification Note
Confirmed fixed facts: P0916AG is DC-DC power supply for I/A Series DCS, 18–36VDC wide DC input, 250W 24VDC output, fanless passive cooling, hot swappable, dual redundant parallel load sharing, fully compatible with all P0914 series hardware, ISA G3 dust resistant; differentiated from AC input P0916AA/AC/AE series.
Unverified content: Original factory full electrical test datasheet, customized explosion-proof versions, ultra-low temperature special industrial variants, which require official Foxboro hardware manual for cross-verification.
Get a Quote