Foxboro P0914XN (FBM213) 8-Channel Galvanic Isolated RTD Temperature Input Module for I/A Series DCS System
Description
3. Product Specification Manual
3.1 Basic Information
Part Number: P0914XN
Corresponding FBM Model: FBM213
Brand: Foxboro (Schneider Electric)
Applicable System: I/A Series DCS Distributed Control System
Core Function: Multi-channel RTD resistance temperature signal acquisition & digital conversion
Input Power: 24VDC (21.6V ~ 25.2V)
Max Power Consumption: 2.8W
Protection Class: IP20
Housing Material: Die-cast aluminum alloy
Compatible Backplane Series: P0914WP, P0914XA, P0914XB, P0914XG
3.2 Signal Acquisition Performance
Input Channels: 8 independent differential RTD channels
Supported RTD Types: Pt100, Pt1000, Cu50, Ni120 standard resistance temperature sensors
Measurement Range: -200℃ ~ +850℃
Measurement Precision: ±0.02% full span at 25℃; temperature reading error ≤ ±0.1℃
Channel Isolation Voltage: 1500V DC between each channel and backplane bus
Excitation Current: Constant low-current excitation to reduce self-heating error of RTD probes
Sampling Mode: Synchronous high-speed sampling for all 8 channels
3.3 Redundancy & Maintenance Features
Hot Swap Support: Plug/unplug online without cutting off cabinet power
Redundancy Configuration: Support dual-module hot standby redundant setup for key process loops
On-board Diagnosis: Real-time detection of open circuit, short circuit, over-range, probe damage; LED status prompt
Bus Communication: High-speed internal differential backplane bus, seamless data interaction with main controller
3.4 Environmental Technical Index
Operating Temperature: 0℃ ~ +60℃
Storage Temperature: -40℃ ~ +85℃
Ambient Resistance: G3 dust-proof, complies with IEC industrial EMI anti-interference standards
Vibration Resistance: Meet IEC60068 industrial anti-vibration test specifications
3.5 Built-in Safety Protection
Independent channel overvoltage & short-circuit automatic protection
Reverse power connection prevention circuit
Built-in RTD linear correction algorithm for accurate temperature conversion
Real-time data parity check to prevent abnormal temperature data uploading
3.6 Step-by-Step Installation Instructions
Vertically insert P0914XN module into dedicated slot of P0914 series backplane inside standard 19-inch control cabinet;
Access 24VDC regulated DC power supply and strictly distinguish positive & negative polarities;
Wire 2-wire/3-wire/4-wire RTD temperature probes to matched TA termination assembly, follow polarity marking;
Tighten all wiring terminals to avoid loose contact causing temperature signal drift;
Power on the control cabinet, launch I/A Series configuration software and select corresponding RTD type for each channel;
Check front panel LEDs: steady green = normal temperature collection, flashing red = channel fault or probe failure.
4. Application Fields
Petrochemical, oil refining & natural gas plants (reactor, pipeline, distillation tower temperature monitoring)
Fine chemical, pharmaceutical and chemical raw material production workshops
Thermal power boilers, turbine units, waste incineration power stations
Steel smelting, non-ferrous metal furnace and heat treatment production lines
Cement rotary kiln, building material calcination and mineral processing industry
Pulp, papermaking, textile drying and food baking processing plants
Municipal sewage treatment, environmental protection flue gas heat monitoring
Industrial park heating stations, HVAC heat exchange automatic control systems
Information Distinction Note
Confirmed fixed facts: P0914XN=FBM213, 8-channel isolated RTD input module, compatible with full P0914 backplane series, supporting hot swap & redundancy, 1500V channel isolation.
Unverified content: Specific original factory calibration parameters, ATEX explosion-proof certification grade, customized special RTD signal expansion functions, which need official Foxboro manual verification.
Get a Quote