FBM41
Description
Foxboro FBM41 (P0400YE) – 60 VDC 8‑Channel Isolated Discrete Input/Output Module
Specifications & User Guide (Copy‑Ready English)
General
Model: FBM41 (P0400YE)
System: Foxboro I/A Series / EcoStruxure Foxboro DCS
Type: 8‑channel isolated discrete (dry contact / 60 VDC) input/output module
Function: On‑off control for valves, motors, solenoids, and status sensing
Redundancy: 1:1 hot‑swap redundant capable
Hot Swap: Supported (no system shutdown)
Certification: CE, UL, CSA, ATEX; Class I Div 2 / Zone 2
Environment: Class G3 (harsh industrial)
Operating Temp: 0 °C to +60 °C
Storage Temp: −40 °C to +85 °C
Humidity: 5–95 % non‑condensing
Enclosure: Die‑cast aluminum, IP20 rated
Dimensions: 140 mm × 165 mm × 45 mm
Weight: 0.65 kg
I/O Channel Specifications
Configuration: 8DI / 8DO (galvanically isolated, channel‑to‑channel & channel‑to‑ground)
Discrete Inputs (8 channels)
Signal Type: Dry contact / 15–60 VDC sense
On‑State: 15–60 VDC; Off‑State: 0–5 VDC
Input Current: 1.4 mA typical @ 5–60 VDC
Debounce: Configurable (0 / 4 / 8 / 16 / 32 ms)
Isolation: 600 VAC (1 min) channel‑to‑channel & channel‑to‑ground
Discrete Outputs (8 channels)
Type: Solid‑state switch (external source, ≤60 VDC)
Rating: 0.25 A / channel (max 2 A total per module)
On‑Resistance: ≤1 kΩ; Off‑Leakage: ≤0.25 mA
Overload Protection: Per channel, auto‑recovery
Isolation: 600 VAC (1 min) channel‑to‑channel & channel‑to‑ground
Status LEDs: 8 channel (ON/FAULT) + module RUN/FAULT
Termination: P0500RY / RH914TG series TA (order separately)
Power
Supply: 24 VDC (±5 % / −10 %), redundant
Consumption: 9 W (single); 14 W (redundant pair)
Heat Dissipation: 8.5 W (single); 13 W (redundant pair)
Communication
Fieldbus: Redundant 2 Mbps backplane (I/A Series)
Protocol: Foxboro proprietary
Data Update: 50 ms (default)
Basic Installation & Usage
Mounting
Snap into standard I/A Series DIN rail or baseplate.
Secure latch; ensure full seating for backplane contact.
Wiring
Connect field devices (contact sensors, solenoids, relays) to TA.
DI: Dry contact or 15–60 VDC; common ground not required (isolated).
DO: External 12–60 VDC source; positive to load, negative to module.
Use shielded twisted pair; separate analog/digital cables.
Wiring size: 0.2–4 mm² (24–12 AWG); ferrules recommended.
Configuration (I/A Series Software)
Set DI debounce time and alarm thresholds.
Configure DO failsafe state (hold / ON / OFF).
Enable diagnostics (open load, short circuit, overcurrent).
Assign redundancy role (primary/secondary) if applicable.
Operation
RUN (green): module ok; FAULT (red): error (comms/power/channel).
Channel LED: ON = active; FLASH = fault (short/open/overload).
Monitor DI status and DO commands in HMI.
Maintenance
Hot‑swap faulty module (no shutdown; TA wiring intact).
Inspect TA wiring, shields, and grounds annually.
Update firmware via I/A Series software.
Calibration: Not required (factory‑calibrated; on‑board diagnostics).
Typical Applications
On/off control for solenoid valves, motor starters, and contactors.
Status monitoring of limit switches, pressure switches, and dry contacts.
Interface to 24–60 VDC discrete devices in process industries.
Migration of legacy FBM03/FBM08 to 200‑series FBMs.

Get a Quote