FBM39
Description
Foxboro FBM39 (P0902UT-0C / P0400YE) – Intelligent Transmitter / 0-20mA Output Interface Module
Specifications & User Guide (Copy‑Ready English)
General
Model: FBM39 (P0902UT‑0C / P0400YE)
System: Foxboro I/A Series / EcoStruxure Foxboro DCS
Type: Intelligent transmitter interface + 0–20 mA analog output module
Function: Connects intelligent transmitters; provides analog output for valves/actuators
Redundancy: 1:1 hot‑swap redundant capable
Hot Swap: Supported (no system shutdown)
Certification: CE, UL, CSA, ATEX; Class I Div 2 / Zone 2
Environment: Class G3 (harsh industrial)
Operating Temp: 0 °C to +60 °C
Storage Temp: −40 °C to +85 °C
Humidity: 5–95 % non‑condensing
Enclosure: Die‑cast aluminum, IP20 rated
Dimensions: 140 mm × 165 mm × 45 mm
Weight: 0.68 kg
I/O & Interface Specifications
Channels: 8 galvanically isolated (mix of intelligent input / analog output)
Signal Types:
Intelligent transmitter input (digital + 4–20 mA HART)
Analog output: 0–20 mA (configurable for 4–20 mA)
Resolution: 13‑bit (AO); 16‑bit (AI)
Accuracy: ±0.05 % FS (AO); ±0.02 % FS (AI)
Isolation: 600 VAC (1 min) channel‑to‑channel & channel‑to‑ground
Load Resistance (AO): 0–750 Ω (20 mA @ 18 VDC compliance)
Short‑circuit & Overload Protection: Per channel (auto‑recovery)
Status LEDs: 8 channel (ON/FAULT/HART) + module RUN/FAULT
Termination: P0500RY terminal plug (included)
Power
Supply: 24 VDC (±5 % / −10 %), redundant
Consumption: 11 W (single); 17 W (redundant pair)
Heat Dissipation: 10.5 W (single); 16.2 W (redundant pair)
Communication
Fieldbus: Redundant 2 Mbps backplane (I/A Series)
Protocol: Foxboro proprietary + HART pass‑through
Data Update: 50 ms (default)
HART Support: HART 5/6/7 (per channel)
Basic Installation & Usage
Mounting
Snap into standard I/A Series DIN rail or baseplate.
Secure latch; ensure full seating for backplane contact.
Wiring
Connect intelligent transmitters (pressure/flow/level) and analog devices to P0500RY termination plug.
Transmitter input: 2‑wire (loop‑powered, HART).
Analog output: 2‑wire to valve/actuator; common ground not required (isolated).
Use shielded twisted pair; separate analog/digital cables.
Configuration (I/A Series Software)
Set channel mode: Intelligent Input (HART) / Analog Output (0–20 mA).
Configure AO range (0–20 mA / 4–20 mA) and scaling.
Enable HART (1200 bps); set NE 43 fault thresholds.
Assign failsafe state (hold / 0 % / 100 %) for AO.
Enable diagnostics (short circuit, open load, HART comms).
Operation
RUN (green): module ok; FAULT (red): error (comms/power/channel).
Channel LED: ON = active; FLASH = fault; HART = HART communication.
Monitor HART PV/SV/diagnostics and AO values in HMI.
Maintenance
Hot‑swap faulty module (no shutdown; wiring intact).
Inspect termination plug wiring/shields/grounds annually.
Update firmware via I/A Series software.
Calibration: Not required (factory‑calibrated; on‑board diagnostics).
Typical Applications
Interface for HART intelligent transmitters (pressure/flow/level/temp).
Analog control outputs for valves, actuators, and VFDs.
Mixed intelligent/analog I/O for skids and package units.
Migration of legacy FBM04/FBM05 to 200‑series FBMs.