FBM30
May 13, 2026

FBM30

Specifications & User Guide (Copy‑Ready English) General Model: FBM30 (Field Bus Module 30) System: Foxboro I/A Series DCS Type: 16‑channel isolated discrete output (DO) module Function: On/off control for valves, relays, contactors, solenoids Redundancy: 1:1 redundant capable Hot Swap: Supported (no system shutdown) Certification: CE, ATEX, CSA; Class 1 Div 2 / Zone 2 Environment: Class G3 (harsh industrial) Operating Temp: 0 °C to +60 °C Storage Temp: −40 °C to +85 °C Humidity: 5–95 % non‑condensing Power: 24 VDC (backplane); 3–6 W typical Dimensions: 32 mm × 117 mm × 132 mm Weight: 0.55 kg

Description

Specifications & User Guide (Copy‑Ready English)

General

Model: FBM30 (Field Bus Module 30)

System: Foxboro I/A Series DCS

Type: 16‑channel isolated discrete output (DO) module

Function: On/off control for valves, relays, contactors, solenoids

Redundancy: 1:1 redundant capable

Hot Swap: Supported (no system shutdown)

Certification: CE, ATEX, CSA; Class 1 Div 2 / Zone 2

Environment: Class G3 (harsh industrial)

Operating Temp: 0 °C to +60 °C

Storage Temp: −40 °C to +85 °C

Humidity: 5–95 % non‑condensing

Power: 24 VDC (backplane); 3–6 W typical

Dimensions: 32 mm × 117 mm × 132 mm

Weight: 0.55 kg

Output Specifications

Channels: 16 galvanically isolated (independent)

Output Type: Solid‑state switch (dry contact / voltage switch)

Voltage Ranges (external source):

15–60 VDC (max 2 A per channel)

120/240 VAC (max 0.5 A per channel)

Isolation: 250 VAC (1 min) channel‑to‑channel & channel‑to‑ground

Response Time: ≤ 10 ms (configurable)

Failsafe: User‑defined (ON/OFF/last state)

Short‑circuit Protection: Per channel (auto‑recovery)

Status Indicators: 16 channel LEDs (ON/OFF/FAULT) + module RUN/FAULT LEDs

Communication

Interface: Redundant 2 Mbps fieldbus (backplane)

Protocol: Foxboro I/A Series proprietary

Data Update: 50 ms (configurable)

Basic Installation & Usage

Mounting

Snap into standard I/A Series rack baseplate.

Ensure full seating and secure latch.

Wiring

Connect field devices to Termination Assembly (TA).

Use external power (15–60 VDC / 120/240 VAC) for outputs.

Separate low‑signal cables from high‑power cables.

Each channel is isolated; no common ground between channels.

Configuration (I/A Series Software)

Set output mode: Normal / Failsafe.

Define failsafe state (ON/OFF) for each channel.

Set response time (10–100 ms).

Enable/disable short‑circuit detection.

Operation

Check module LEDs: RUN (green) = ok; FAULT (red) = error.

Check channel LEDs: ON = output active; FLASH = fault.

Monitor status in HMI; acknowledge alarms.

Maintenance

Hot‑swap faulty module (no shutdown required).

Inspect TA wiring and fuses periodically.

Update firmware via I/A Series software.

Typical Applications

On/off control of motor starters, solenoid valves, and contactors.

Alarm annunciation and interlock systems.

Lighting and HVAC control in industrial facilities.

Replacement for legacy FBM29 or FBM27 modules in I/A Series migrations.

Foxboro22.jpg