Description
FBM24C / FBM25C
General Information
Manufacturer: Foxboro (Schneider Electric)
Model: FBM24C / FBM25C
Series: I/A Series EcoStruxure DCS Compact 200 Series
Type: 16‑Channel Isolated Discrete Output Module
Function: Interfaces DCS control signals to field discrete devices (valves, relays, indicators)
Environmental Rating: Class G3 harsh industrial environment (ISA S71.04)
Certification: CE, ATEX, CSA; Class 1 Division 2 / Zone 2 hazardous area approved
Protection Class: IP20
Dimensions (mm): 140 (H) × 165 (W) × 45 (D)
Weight: Approx. 600 g
Key Specifications
Channel Quantity: 16 galvanically isolated discrete output channels
Isolation: Per‑channel galvanic isolation (channel‑to‑channel, channel‑to‑ground)
Output Rating (External Powered):
15–60 VDC, up to 2 A per channel
120 VAC / 125 VDC, up to 0.5 A per channel
240 VAC, up to 0.5 A per channel
On‑state Voltage Drop: ≤ 0.2 V @ 2.25 A
Off‑state Leakage Current: ≤ 0.1 mA
Module Power: 24 VDC (+5% / −10%)
Power Consumption: ≤ 3 W
Operating Temperature: 0°C to +60°C
Storage Temperature: −40°C to +85°C
Humidity: 5%–95%, non‑condensing
Withstand Voltage: 600 VAC for 1 minute (channel‑to‑ground/channel‑to‑channel)
Main Features
16 Fully Isolated Output Channels: Eliminates crosstalk and fault propagation between channels.
Multi‑Voltage Compatibility: Supports 15–60 VDC, 120/240 VAC, and 125 VDC external power.
Configurable Operation:
Fail‑safe mode (hold, off, or preset state)
Sustained or momentary (pulse) outputs
Software‑selectable debounce filtering
Hot Swappable: Online replacement without system shutdown.
Redundancy Ready: Supports 1:1 redundant pairing for high availability.
LED Diagnostics: Front‑panel LEDs for module status and per‑channel indication.
Ladder Logic Support: Executes discrete I/O or ladder logic programs locally.
Versatile Termination Assemblies (TAs): Offer current limiting, fusing, relay/solid‑state outputs, and redundant power distribution.
Applications
Process Industries: Chemical, power, oil & gas, water treatment, and pharmaceuticals.
Discrete Control: On/off control of valves, relays, contactors, alarm lights, and interlock loops.
Harsh & Hazardous Areas: Class G3 environments and Class 1 Div 2/Zone 2 classified locations.
High‑Reliability Systems: Applications requiring redundancy, hot‑swap capability, and advanced diagnostics.