FBM24B/25B
Description
FBM24B / FBM25B
General Information
Manufacturer: Foxboro (Schneider Electric)
Model: FBM24B / FBM25B
Series: I/A Series EcoStruxure DCS Compact 200 Series
Type: 16‑Channel Isolated Discrete Input Module (Expansion Input Module)
Function: Reads discrete contact/voltage signals from field devices (switches, relays, sensors)
Environmental Rating: Class G3 harsh industrial environment (ISA S71.04)
Certification: CE, ATEX, CSA; Class 1 Division 2 / Zone 2 hazardous area approved
Protection Class: IP20
Weight: Approx. 600 g
Dimensions (mm): 140 (H) × 165 (W) × 45 (D)
Key Specifications
Channel Quantity: 16 galvanically isolated discrete input channels
Isolation: Per‑channel galvanic isolation (channel‑to‑channel, channel‑to‑ground)
Input Voltage Ranges (External Excitation):
24 VDC (FBM24B: contact sense)
48 VDC / 125 VDC (FBM25B: voltage sense)
120 VAC / 240 VAC (via termination assemblies)
Input Current: 2–10 mA (per channel, depending on voltage)
Input Filter: Software‑configurable (debounce time)
Module Power: 24 VDC (+5% / −10%)
Power Consumption: ≤ 3 W
Operating Temperature: 0°C to +60°C
Storage Temperature: −40°C to +85°C
Humidity: 5%–95%, non‑condensing
Withstand Voltage: 600 VAC for 1 minute (channel‑to‑ground/channel‑to‑channel)
Main Features
16 Fully Isolated Input Channels: Prevents crosstalk and fault propagation.
Multi‑Voltage Compatibility: Supports 24/48/125 VDC and 120/240 VAC inputs via TAs.
Contact Sense & Voltage Sense: FBM24B for dry contacts; FBM25B for voltage‑based inputs.
Configurable Debounce Filter: Eliminates false triggers from contact bounce.
Hot Swappable: Online replacement without system shutdown.
Redundancy Support: 1:1 redundant pairing for high availability.
LED Diagnostics: Front‑panel LEDs for module status and per‑channel indication.
Fault‑Tolerant Operation: Works with FCP280 for patented fault‑tolerant control.
Applications
Process Industries: Chemical, power, oil & gas, water treatment.
Discrete Input Monitoring: Valve position switches, limit switches, relay contacts, alarm inputs.
Hazardous & Harsh Environments: Class G3, Class 1 Div 2/Zone 2 areas.
High‑Reliability Systems: Requires redundancy, hot‑swap, and advanced diagnostics.

Get a Quote