Bently 3300/20-02-01-01-00-00 Dual Channel Thrust Position Monitor (Product Description)
Description
Bently 3300/20-02-01-01-00-00 Dual Channel Thrust Position Monitor (Product Description)
I. Product Overview
The Bently 3300/20-02-01-01-00 is a dual-channel thrust position monitoring module in the 3300 series mechanical protection system of Bently Nevada (now part of GE). It is used to continuously monitor the axial displacement (thrust gap) of rotating machinery rotors, warning of thrust bearing failure, axial movement, dynamic friction and other faults. It is widely used in key units such as steam turbines, centrifugal compressors, gas turbines, and large pump sets for protection and condition monitoring.
Code meanings of the model:
3300/20: Basic model, dual-channel thrust position monitor;
02: Range ±30 mil (±0.762 mm);
01: Compatible with 3300/7200 series eddy current preamplifiers, sensitivity 200 mV/mil;
01: Alarm relay is epoxy resin sealed type (non-sealed type is 02);
00: No dangerous relay output (only warning, no hard contact for tripping);
00: No safety barrier (non-ia type, used in non-explosion-proof areas).
II. Working Principle
Based on the eddy current measurement principle, it is equipped with 3300/7200 series eddy current probes and preamplifiers: The probe is aligned with the thrust disk of the rotor, converting the axial gap change into high-frequency impedance changes, and the preamplifier linearly converts them into 0–24 VDC gap voltage signals and sends them to the monitor. The module independently samples, filters and calculates the dual-channel signals, and outputs the axial displacement value in real time; compared with the user-defined alarm threshold, if it exceeds the limit, the warning relay is driven to act; this model has no dangerous trip relay, only providing warning without directly triggering shutdown. The dual channels support redundant installation and can be configured with "AND/OR" logic to reduce false alarm risks, in line with API 670 standards.
III. Core Functions
Dual-channel independent monitoring: 2 completely independent axial displacement measurement channels, which can be separately configured with ranges and alarm thresholds; a single-channel failure does not affect the normal operation of the other channel, improving the monitoring continuity.
Precise measurement and real-time display: The measurement accuracy reaches ±0.33% of the full scale (typical), with a maximum error of ≤±1% of the full scale; frequency response DC–1 kHz, covering low-speed to high-speed rotating machinery; the front panel displays the displacement value (mil/mm) and channel status in real time.
Single-level warning protection: Equipped with epoxy resin sealed type warning relay (Alert), dust-proof, moisture-proof, and vibration-resistant; no dangerous (Danger) relay; customizable alarm thresholds, triggering the relay output when the displacement exceeds the limit, used for DCS/PLC alarms or audible and visual prompts, without direct tripping.
Standard signal output: Provides 4–20 mA analog output (optional 0–10 VDC), linearly corresponding to the full range of displacement, suitable for various recorders, DCS/PLC systems, for remote monitoring and data acquisition.
Comprehensive self-diagnosis: Real-time monitoring of probe circuit breakage / short circuit, preamplifier signal abnormality, module power supply and internal circuit faults; when a fault occurs, the output is locked and the front panel fault light is illuminated to avoid false alarms.
IV. Technical Parameters
Model: 3300/20-02-01-01-00-00
Type: Dual-channel thrust position monitoring module
Measurement parameters: Rotor axial displacement (thrust position)
Range: ±30 mil (±0.762 mm, code 02)
Compatible sensor: 3300/7200 eddy current preamplifier, sensitivity 200 mV/mil (code 01) Measurement accuracy: ±0.33% of full scale (typical), ±1% of full scale (maximum)
Frequency response: DC–1 kHz
Channel quantity: 2 independent inputs
Alarm configuration: 1 epoxy resin sealed warning relay (code 01), no hazardous relay (code 00)
Analog output: 4–20 mA (default)/0–10 VDC (optional), accuracy ±0.1%
Probe power supply: -24 VDC (provided by the module internally)
Operating power: 110/220 VAC, 50/60 Hz
Power consumption: ≤5.5 W (typical)
Operating temperature: 0℃~+60℃
Storage temperature: -40℃~+85℃
Humidity: 5%–95% (no condensation)
Size: 165 mm×114 mm×64 mm (width × height × depth)
Weight: Approximately 1.1 kg
Certifications: CE, UL, CSA, compliant with API 670 standard
Installation method: Standard 19-inch rack slot installation of the 3300 series
V. Model Configuration Description
3300/20: Dual-channel thrust position monitor (core function)
02: ±30 mil full scale (±0.762 mm)
01: Compatible with 3300/7200 preamplifier, 200 mV/mil
01: The alarm relay is epoxy resin sealed (dustproof, moistureproof, vibration-resistant)
00: No hazardous relay (only warning, no trip output)
00: No safety barrier (non-explosion-proof design, for general industrial environments)
VI. Application Scenarios
Power industry: Thermal power / nuclear power turbine, generator rotor axial displacement warning monitoring;
Petroleum industry: Centrifugal compressor, ethylene / propylene unit, large pump set thrust bearing condition monitoring;
Metallurgical industry: Blast furnace blower, sintering main exhaust fan, etc. high-speed rotating equipment;
General machinery: Large motors, gas turbines, screw compressors, etc. key units' non-trip protection.
VII. Installation and Maintenance Tips
Installation: Standard 3300 rack vertical slot installation, ensure good heat dissipation; probe installed above the thrust disk, initial gap controlled within 0.5–2.5 mm, avoid oil and water vapor erosion.
Wiring: Connect the preamplifier and the monitor with high-frequency coaxial cable, length ≤5 m; Analog output uses shielded twisted pair, single-ended grounding, keep away from power cables to reduce electromagnetic interference.
Calibration: At least calibrate once a year, use a standard displacement simulator to verify the range, accuracy and alarm threshold, ensure error ≤±1% of full scale.
Maintenance: Regularly check probe gap, cable insulation and relay contacts; prioritize troubleshooting the probe circuit, preamplifier power supply and signal status when there is a self-diagnostic alarm.
VIII. Advantages and Features
High reliability: Epoxy resin sealed relay, wide temperature design, anti-electromagnetic interference, suitable for harsh industrial environments;
Safe warning design: No hard trip contacts, only provides warning signals, avoiding machine stoppage due to false shutdown;
Easy integration: Standard 4–20 mA signal output, compatible with mainstream DCS/PLC, quick integration into existing systems;
Redundant safety: Dual-channel independent monitoring + self-diagnosis, effectively reducing false alarms / missed alarms risk;
Long life: Industrial-grade components, no wear parts, normal maintenance life ≥10 years.