TAS10A040-N06-4X1-1 MOVITRANS® TAS10A Transformer Module(SEW‑EURODRIVE)
Description
1.1 Product Overview
1.2 Model Code Definition
TAS10A: Series designation (TAS = Transformer Module, 10A = Series)
040: Size 2, 4 kVA nominal power
N06: Primary voltage 400 V AC, 50/60 Hz
4X1: Secondary voltage 4 × 115 V AC
1: Standard version, no options
1.3 Safety Instructions
2. Technical Specifications
2.1 Electrical
Nominal Power: 4 kVA
Primary Voltage: 400 V AC ±10%, 50/60 Hz
Secondary Voltage: 4 × 115 V AC
Primary Current: 10 A max
Secondary Current: 4 × 8.7 A max
Insulation Class: Class F (155 °C)
Dielectric Strength: 2 kV AC, 1 min (primary‑secondary)
Protection Class: IP20 (touch‑safe, protected against solid objects >12 mm)
2.2 Mechanical & Environmental
Housing: Compact metal enclosure, black painted
Dimensions (W×H×D): 200 mm × 150 mm × 80 mm
Mounting: Wall‑mount or panel‑mount (4 × M4 holes)
Operating Temperature: 0 °C to +40 °C
Storage Temperature: −25 °C to +70 °C
Relative Humidity: 5%–95% (non‑condensing)
Weight: Approx. 8 kg
3. Installation
3.1 Mechanical Mounting
3.2 Electrical Connection
Primary Side: Connect 400 V AC supply to terminals L1, L2, L3, PE.
Secondary Side: Connect loads to terminals 115 V‑1, 115 V‑2, 115 V‑3, 115 V‑4, and common neutral.
Grounding: Ensure PE terminal is connected to protective earth.
Cable Size: Primary: 1.5–2.5 mm²; Secondary: 1.5 mm².
Torque: Tighten terminal screws to 1.2 N·m.
4. Operation
4.1 Initial Start‑Up
4.2 Operating Limits
5. Maintenance
5.1 Regular Inspection
Check all terminals for tightness and corrosion.
Clean dust from ventilation slots with a dry brush.
Inspect cables for damage or aging.
5.2 Lubrication
5.3 Replacement Parts
6. Troubleshooting
No secondary voltage: Check primary power, fuse, and wiring; verify terminal connections.
Low secondary voltage: Overloaded secondary circuit; reduce load.
Overheating: Insufficient ventilation, overloaded, or shorted secondary.
Abnormal hum: Loose core, damaged winding, or incorrect voltage.
7. Ordering Information
Model: TAS10A040-N06-4X1-1
Accessories: Mounting brackets, cable glands, protective covers available separately.
Get a Quote