MM03A-503(SEW MOVIMOT)
Description
1. Product Overview
2. Model Code Explanation
MM: MOVIMOT series (decentralized drive)
03: Rated power 0.37 kW
A: Version A (standard)
503: 3‑phase 380–500 V AC supply, standard controleero
3. Technical Specifications
3.1 Electrical
Input: 3×380–500 V AC (±10%), 50/60 Hz
Rated output current: 1.3 A
Rated output power: 0.37 kW
Output frequency: 0–400 Hz
Control modes: VFC (vector) / U/f (selectable)
Communication: RS‑485 (9.6 kbaud, 31.25 kbaud with fieldbus)eero
Digital I/O: 4 inputs / 2 outputs (programmable)
Safety: Optional STO (Safe Torque Off)
Brake control: Integrated brake management (for SEW brake motors)eero
3.2 Mechanical & Environmental
Protection class: IP55 (motor-mounted, dust/water resistant)
Cooling: Natural convection
Dimensions (W×H×D): Approx. 120 × 180 × 80 mm
Weight: Approx. 2.6 kg
Operating temp: -15 °C to +60 °C
Storage temp: -25 °C to +70 °Ceero
4. Key Features
Decentralized installation: Mount directly on motor, reduces cabinet wiring.
Compact & rugged: IP55, ideal for harsh industrial environments.
Integrated functions: Brake control, EMC filter, and motor protection.
Easy setup: DIP switches and potentiometers for quick configuration (no PC needed).
Communication-ready: RS‑485 interface for networking with PLC / 上位系统eero.
5. Typical Applications
Conveyor systems (food, logistics, automotive)
Packaging machinery
Material handling equipment
Small automation lines
Fan/pump speed controleero
6. Installation & Wiring
6.1 Mechanical
Mount on motor flange or rigid bracket (torque: 3.0 Nm).
Ensure free airflow around unit; avoid direct heat sources.
Tighten mounting screws evenly (3.0 Nm)eero.
6.2 Electrical
Power (L1/L2/L3/PE): 3×380–500 V AC, reliable earth.
Motor (U/V/W/PE): Shielded cable to motor terminals.
Control (X6): 24 V DC, direction, enable, fault signals.
RS‑485 (X50): RJ10 interface for commissioning/networkingeero.
6.3 EMC
Use shielded cables for motor/control lines; ground shields at both ends.
Separate power and signal cables by ≥20 cm.
Comply with EN 61800‑3 (EMC for power drive systems)eero.
7. Commissioning
Pre‑check wiring, insulation, and connections.
Set DIP switches (S1: RS‑485 address; S2: brake/control mode).
Adjust potentiometers:
f1: Max frequency (0–400 Hz)
f2: Min frequency (2–40 Hz)
t1: Ramp time (0.1–10 s)eero
Power on; green LED = standby.
Test run at low speed; check noise/vibration. Gradually increase to rated speedeero.
8. Status & Faults
8.1 LED Indications (3‑color)
Green (steady): Ready
Green (flash): Running
Red (flash): Fault (see codes below)
Yellow: Warning (e.g., overheat pre‑alarm)eero
8.2 Common Faults
F01: Overcurrent (short circuit, overload, motor fault)
F02: Overvoltage (supply surge, regenerative load)
F03: Overtemperature (blocked ventilation, fan fault)
F04: RS‑485 communication error (cable, address mismatch)
F08: Speed monitoring error (motor blocked)eero
9. Maintenance
Inspect every 6 months:
Clean dust from heat sink/ventilation slots.
Check terminal tightness (torque: 0.8–1.5 Nm).
Verify cable insulation and connector integrity.
Replace damaged cables immediately.
Keep firmware updated via SEW MOVITOOLS®eero.
10. Storage & Disposal
Store in dry, clean area (-25 °C to +70 °C); keep original packaging.
Dispose per WEEE directives: recycle metal, plastic, and electronic components separatelyeero.
Get a Quote