MDX61B0150-503-4-00 MOVIDRIVE® B Series AC Drive (SEW‑EURODRIVE)
Description
1. General Description
Model: MDX61B0150-503-4-00
Manufacturer: SEW‑EURODRIVE
Series: MOVIDRIVE® MDX61B (Size 3)
Rated Power: 15 kW (Constant Torque, CT)
Type: Standard industrial drive, no integrated EMC filter, non‑conformal coated PCB, for clean indoor environments.
2. Model Code Explanation
MDX61B: MOVIDRIVE B series, dual expansion slots (encoder + fieldbus)
0150: Rated power 15 kW
503: 3‑phase 380–500 V AC, without built‑in EMC filterSEW-EURODRIVE
4: Internal brake chopper, four‑quadrant regenerative operation
00: Standard version, non‑coated PCB, clean/dry environments
3. Technical Specifications
3.1 Electrical Ratings
Input Voltage: 3×380–500 V AC (‑15% / +10%), 50/60 HzSEW-EURODRIVE
Rated Input Current: 28.8 A
Rated Output Power: 15 kW (CT)
Rated Output Current: 32 A
Apparent Power: 22.2 kVA
Output Frequency: 0–599 Hz
Control Modes: VFC (V/f), CFC (closed‑loop vector), Servo control
Overload: 150% / 60 s; 200% / 1 s
Switching Frequency: 4/8/12/16 kHz (adjustable)
Safety: STO (Safe Torque Off), PL d / SIL 2
3.2 Mechanical & Environmental
Protection Class: IP20 (cabinet mount only)
Dimensions (W×H×D): 200 × 465 × 308 mm
Weight: ~15 kg
Operating Temp: 0 °C to +45 °C (derate above 40 °C)
Storage Temp: ‑25 °C to +70 °C
PCB Protection: Non‑coated (standard 00)
Altitude: ≤1000 m no derating; 1% / 100 m above 1000 m
Certifications: CE, UL, RoHS, EAC
4. Main Features
No Internal EMC Filter (503): For systems with external EMC filters (C1/C2)SEW-EURODRIVE.
Four‑Quadrant Operation: Built‑in brake chopper for regenerative braking.
IPOSplus® Motion: Positioning, electronic gearing, master‑slave sync; application modules (winding, flying saw).
Modular Design: Expandable via encoder (DEU21B) and fieldbus modules (PROFINET, EtherCAT).
Standard PCB: Non‑coated, cost‑effective for clean industrial areas.
5. Installation & Wiring
Mounting: Vertical in control cabinet.
Clearance: ≥100 mm top/bottom, ≥50 mm sides.
Main Terminals:
X1: L1, L2, L3, PE (mains)
X2: U, V, W, PE (motor)
X4: +UZ, –UZ, PE (DC link, external brake resistor)
X11: Analog input (0–10 V / 4–20 mA)
X13: 24 V DC digital I/O
X15/X16: Encoder interfaces
6. Operation & Commissioning
Local: DBG60B keypad (parameters, run/stop, fault display).
PC: MOVITOOLS® MotionStudio (programming, monitoring, diagnostics).
Modes: Jog, reference homing, positioning, synchronous operation.
7. Safety Notes
Install/wire only by qualified electricians.
High voltage remains ≥5 min after power‑off; wait for discharge before servicing.
Use shielded cables for motor/signal wiring; add external EMC filter per 503 designSEW-EURODRIVE.
8. Maintenance & Troubleshooting
Routine: Check connections/ventilation; clean dust with dry compressed air.
Common Faults: OC (overcurrent), OV (overvoltage), OT (overtemp), encoder error.
9. Applications
Conveyors, cranes, hoists
Packaging, textile, woodworking machinery
Fans, pumps, process equipment
Clean environments: Indoor industrial sites with external EMC planningSEW-EURODRIVE.
10. Version Comparison (15 kW Models)
00: Non‑coated PCB, no internal filter → clean environments + external EMCSEW-EURODRIVE
0T: Conformal coated PCB, no internal filter → humid/dusty environments
5A3: Non‑coated PCB, integrated C2 filter → clean environments, no external filter needed