MDX61B0014-5A3-4-0
Description
1.1 Product Overview
1.2 Model Decoding
MDX61B: High‑performance drive with two option slots (encoder + fieldbus).
0014: Rated motor power = 1.5 kW.
5A3: 5 = 380–500 V AC; A = Class C2 EMC filter; 3 = three‑phase input.
4: Integrated brake chopper (4‑quadrant operation).
0: Standard version (non‑coated PCB, basic motion functions).
1.3 Safety Symbols
DANGER: High voltage inside—risk of electric shock.
WARNING: Potential personal injury or equipment damage.
CAUTION: Minor injury or component fault risk.
NOTE: Important operation/maintenance tips.
1.4 Intended Use
1.5 Warranty
2. Technical Specifications
2.1 Electrical Data (3 × 380–500 V AC, 50/60 Hz)
Rated input current: 3.6 A
Rated output power: 1.5 kW (constant torque) / 2.2 kW (variable torque)
Rated output current: 4.0 A
Apparent power: 2.8 kVA
Output frequency: 0–599 Hz
Overload capacity: 200% / 60 s; 175% / 2 seero
PWM carrier frequency: 4 kHz (default); 8/16 kHz selectableeero
Brake chopper: Integrated (external resistor ≥ 68 Ω required)eero
EMC filter: Class C2 (EN 61800‑3)
Protection class: IP20 (install in control cabinet)eero
2.2 Mechanical & Environmental
Dimensions (W×H×D): 105 × 260 × 95 mm
Weight: ~2.8 kg
Cooling: Temperature‑controlled forced aireero
Operating temperature: 0 °C to +50 °C (derate > 40 °C)eero
Storage temperature: −25 °C to +70 °C
Altitude: ≤ 1000 m (no derating); > 1000 m: −1% per 100 m
PCB: Standard (non‑coated)
2.3 Control Modes & Interfaces
VFC (V/f): Open‑loop, general speed control.
CFC: Closed‑loop vector, high torque/accuracy.
Servo: With encoder, for permanent magnet motors.
IPOSplus®: Basic positioning, electronic cam, master‑slave sync, flying restart, DC braking.
PID controller: For flow/pressure closed‑loop controleero.
Analog inputs: ±10 V, 4–20 mAeero.
Digital inputs: 6 × 24 V DC isolatedeero.
Digital outputs: 2 × transistor, 1 × relayeero.
Motor thermistor input (PTC)eero.
Communication: SBus, RS485 (Modbus RTU).
Option slots: Encoder (e.g., DEH11B) + fieldbus (e.g., PROFINET, CANopen).
2.4 Safety & Protection
STO (Safe Torque Off): PL d complianteero.
Protection: Overcurrent, overvoltage, undervoltage, overtemperature, ground fault, short circuit, motor overtemperature (PTC)eero.
Fault response: Alarm + safe stop; fault code displayed on 7‑segment LEDeero.
3. Installation
3.1 Unpacking & Inspection
Check for physical damage (dents, scratches).
Verify model: MDX61B0014-5A3-4-0.
Confirm accessories: Mounting screws, terminal covers, manual.
3.2 Mounting
Install vertically in clean, dry, ventilated cabineteero.
Clearance: 100 mm top/bottom for airfloweero.
Avoid direct sunlight, heat sources, corrosive gases.
Fix with M4 screws; torque 1.2–1.5 Nmeero.
3.3 Wiring
L1/L2/L3: 3 × 380–500 V AC inputeero.
PE: Protective eartheero.
U/V/W: Motor outputeero.
+R/−R: External brake resistoreero.
X10: Digital inputs (24 V DC).
X11: Digital outputs.
X12: Analog inputs.
X13: PTC thermistor.
X14: Encoder (option).
X15: SBus/RS485.
X17: STO safety inputeero.
Separate power and signal cables (≥ 20 cm)eero.
Use shielded cables for signals; ground shields at both endseero.
Torque terminals to 0.8–1.0 Nmeero.
Recheck all connections before power‑oneero.
4. Commissioning
4.1 Pre‑Start Check
All wiring correct and tighteero.
Terminal covers installedeero.
No foreign objects in cabineteero.
Ambient conditions within limitseero.
4.2 Basic Parameter Setup (via DBG60B keypad or MOVITOOLS®)
Set motor data (nameplate):
Rated power: 1.5 kW.
Rated voltage: 400 V.
Rated current: ~4.0 A.
Rated frequency: 50 Hz.
Rated speed: 1450 rpm.
Select control mode (VFC/CFC/Servo).
Set frequency limits: Min 0 Hz, Max 50 Hz (default)eero.
Accel/decel time: 5 s (default)eero.
Configure I/O functions (e.g., start/stop, speed reference)eero.
Run auto‑tuning (CFC/Servo mode)eero.
4.3 Operation
Jog mode: Test motor rotation and speed.
No‑load run: Check for noise, vibration, overheatingeero.
Loaded run: Gradually apply load; monitor current/tempeero.
Long‑term: Check parameters periodically; clean fan/filterseero.
5. Maintenance & Troubleshooting
5.1 Maintenance
Power off and wait 10 min before maintenance (capacitor discharge)eero.
Clean dust from heat sink/fan every 3–6 monthseero.
Check terminal tightness and cable insulationeero.
Replace damaged cables immediatelyeero.
5.2 Common Faults
Overvoltage (F01): High supply voltage; regenerative loadeero.
Undervoltage (F02): Low supply; loose wiringeero.
Overcurrent (F03): Short circuit; motor overloadeero.
Overtemp (F04): Dirty fan; high ambient tempeero.
Motor overtemp (F05): PTC trip; motor overloadeero.
Ground fault (F06): Cable/motor insulation failureeero.
6. Compliance & Certifications
CE (EN 61800‑3, EN 60204‑1)eero.
UL 508C, CSAeero.
RoHS complianteero.
7. Version Notes
‑0: Standard non‑coated PCB, basic motion functions, for clean/dry environments.
‑0T: Conformal coated PCB, advanced motion, for harsh environments (dust/moisture).