MDV60A0220-503-4-00 (SEW MOVIDRIVE 60A Inverter)
Description
Technical Specifications
Input: 3-phase AC 380–500 V, 50/60 Hz, 41.4 A
Output: 22 kW, 46 A, 51.7 kVA, frequency 0–180 Hz
Control Modes: VFC (open-loop vector), CFC (closed-loop vector, with encoder)
Overload Capacity: 150% / 60 s; 200% / 3 s
Protection Class: IP20 (cabinet mounting)
Ambient Temperature: 0 °C to +40 °C (full load)
Dimensions (W×H×D): 200 × 470 × 221 mm
Weight: 15 kg
Key Features
No built-in RFI filter, ideal for systems with external EMC filtering
4-quadrant design enables fast braking and energy recovery
Standard firmware for general-purpose industrial drives
Supports VFC/CFC vector control for high-precision motor regulation
Compatible with PROFIBUS, CANopen, Modbus, and SBus communication protocols
Comprehensive protection: overvoltage, overcurrent, overtemperature, stall, earth fault
Typical Applications
Heavy-duty conveyors and bulk material handling
Industrial fans, pumps, and process machinery
General automation with external EMC infrastructure
High-power asynchronous motor speed/torque control
Related Model Variants
MDV60A0220-5A3-4-00: 22 kW, with integrated RFI filter
MDV60A0220-503-4-0T: 22 kW, no RFI filter, application firmware
MDV60A0220-503-4-06: 22 kW, no RFI filter, conformal coated PCB (harsh environments)
Get a Quote