31C022-503-4-05
Description
Model Code Explanation
31C: MOVITRAC 31C series, compact regenerative drive
022: Rated power 3.0 kW, rated output current 6.5 A
503: 3-phase 380–500 V AC input, no built-in EMC filter
4: 4-quadrant operation with regenerative braking and grid energy feedback
05: Standard firmware with STO safety function, no fieldbus module
Technical Specifications
Input
Rated voltage: 3-phase AC 380–500 V (±10%)
Input frequency: 50 / 60 Hz (±10%)
Rated input current: 5.8 A
Output
Rated power: 3.0 kW
Rated output current: 6.5 A
Apparent power: 4.5 kVA
Frequency range: 0–400 Hz
Overload capacity: 125% rated current for continuous operation; 150% rated current for 60 seconds
Control & Interfaces
Control modes: V/F open-loop control, sensorless vector control (VFC)
Digital I/O: 6 digital inputs, 2 digital outputs, 1 relay output
Analog I/O: 2 analog inputs, 2 analog outputs
Safety function: STO (Safe Torque Off), compliant with EN 61508 SIL 2 and EN 60204-1 Category 3
Protection functions: Overcurrent, overvoltage, undervoltage, overtemperature, earth fault and short circuit protection
Mechanical & Environmental Data
Protection class: IP20
Operating temperature: 0 °C to +45 °C. Power derating is required above 40 °C.
Storage temperature: -25 °C to +70 °C
Dimensions (W×H×D): approx. 127 × 165 × 178 mm
Weight: approx. 2.2 kg
Key Features
- 4-quadrant energy regenerationBraking energy is recycled to the grid. No external brake resistor is required to cut costs and save installation space.
- Built-in STO safety functionThe integrated Safe Torque Off complies with industrial safety standards, which can reliably disable motor torque to protect personnel and equipment.
- Compact designThe small size enables easy installation inside standard control cabinets.
- Stable performance & comprehensive protectionTwo control modes ensure steady speed and torque output. Multiple protection functions guarantee long-term reliable operation.
Typical Applications
Related Models
31C022-503-4-00: 3.0 kW, 4-quadrant regenerative inverter, no STO and no fieldbus
31C022-503-4-20: 3.0 kW, 4-quadrant regenerative inverter with PROFIBUS-DP
31C022-503-4-25: 3.0 kW, 4-quadrant regenerative inverter with PROFIBUS-DP and STO