3015KPM
May 20, 2026

3015KPM

Part Number: 3015KPM Manufacturer: XYCOM Automation (Schneider Electric / Pro‑face) Product Type: 15" Industrial Flat‑Panel Monitor / Operator Interface (KPM = Keyboard/Panel‑Mount) Series: 3015 Series (rugged industrial display) Status: EOL (Discontinued; available as refurbished/used) Weight: ~6.3 kg (14 lbs)

Description

1. General Information

  • Part Number: 3015KPM

  • Manufacturer: XYCOM Automation (Schneider Electric / Pro‑face)

  • Product Type: 15" Industrial Flat‑Panel Monitor / Operator Interface (KPM = Keyboard/Panel‑Mount)

  • Series: 3015 Series (rugged industrial display)

  • Status: EOL (Discontinued; available as refurbished/used)

  • Weight: ~6.3 kg (14 lbs)

2. Product Description

The 3015KPM is a NEMA 4/4X/12‑sealed 15‑inch industrial monitor with integrated membrane keypad and touchscreen, designed for panel‑mount deployment in factory automation and harsh environments. It serves as a rugged operator interface for XYCOM 2000/2225 series workstations and VMEbus systems.

3. Hardware Specifications

Display

  • Screen: 15" Industrial Color TFT LCD

  • Resolution: 1024 × 768 (XGA)

  • Brightness: 350 cd/m² (typical)

  • Contrast Ratio: 400:1 (typical)

User Interface

  • Touchscreen: 5‑wire resistive, NEMA 4/4X sealed

  • Keypad: Integrated 40‑key relegendable membrane keypad

  • Pointing Device: Industrial trackball (optional)

Electrical

  • Input Voltage: 100–240 VAC, 50/60 Hz, 0.6 A

  • Power Supply: Internal, wide‑range switching

  • Protection: Overvoltage, overcurrent, EMI filtering

I/O Ports

  • Video: VGA (DB15, 15‑pin)

  • Touchscreen: RS‑232 serial (DB9)

  • Keyboard/Mouse: PS/2 (rear)

  • USB: Front USB 1.1 port

Mechanical & Environmental

  • Dimensions: 482.6 × 367.2 × 101.6 mm (19.0 × 14.5 × 4.0 in)

  • Mounting: Panel mount (19” rack‑compatible)

  • Front Panel: NEMA 4/4X/12, IP65 sealed

  • Operating Temp: 0 °C to +55 °C

  • Storage Temp: −40 °C to +85 °C

  • Humidity: 10%–90% non‑condensing

  • Vibration: 0.1 g (5–2000 Hz)

  • Certifications: CE, FCC Class A, UL 508, Class I Div 2 hazardous location rated

4. Compatibility

  • Host Systems: XYCOM 2000T/2050T, 2225‑0036, VMEbus CPUs (XVME‑654/655)

  • OS Support: Windows 2000/XP, DOS, QNX, VxWorks

  • Touchscreen Drivers: Windows, DOS, QNX (included)

5. Installation & Maintenance

  1. Mounting: Secure to panel; maintain NEMA 4 seal with proper gasket torque。

  2. Wiring: Separate power and signal cables (≥10 cm) for EMI reduction。

  3. Cleaning: Use mild, non‑residue cleaners; avoid harsh chemicals。

  4. Calibration: Calibrate touchscreen quarterly (via OSD or driver utility)。

6. Availability

  • Original: Discontinued by Schneider Electric。

  • Spare Parts: Refurbished, tested units and surplus stock available。

  • Replacement: Succeeded by Pro‑face PS/5000 series industrial HMIs。


Get a Quote