ABB AF26Z-30-11-21 1SBL236001R2111: AF26Z Three-Pole Contactor Product Description
Description
ABB AF26Z-30-11-21 1SBL236001R2111: AF26Z Three-Pole Contactor Product Description
Brand and Product Identification
The ABB AF26Z-30-11-21, ABB product ID 1SBL236001R2111 and EAN 3471523114210, is a three-pole block contactor from the ABB AF26Z low-consumption contactor series. The AF prefix identifies the AF electronic coil contactor family, Z identifies the low-consumption Z variant, 26 identifies the AF26 frame size, 30 identifies three main poles, 11 identifies one built-in NO auxiliary contact and one built-in NC auxiliary contact, and -21 identifies the 24 to 60 V AC and 20 to 60 V DC coil variant. The contactor has pre-mounted auxiliary contacts and screw terminals, designed for controlling three-phase motors, non-inductive loads and slightly inductive loads.
Product Function and System Role
The AF26Z-30-11-21 switches and isolates a three-phase power circuit when the electronic coil is energized by the control circuit. The three main NO contacts close to connect the motor or load to the supply, while the built-in NO and NC auxiliary contacts provide control feedback, interlocking or indication signals. The contactor is controlled by PLC outputs, pushbuttons, relays, motor protection devices or automation control signals. It is a power switching contactor, not a motor-protective circuit breaker, overload relay, soft starter, drive, PLC or disconnect switch by itself.
Main Circuit Ratings
The contactor has three main NO poles. Rated operational voltage for the main circuit is 690 V AC according to IEC, or 600 V according to UL and CSA. Conventional free-air thermal current Ith is 50 A at temperatures up to 40 degrees Celsius. AC-1 rated operational current is 45 A at 690 V and up to 40 degrees Celsius, 40 A at up to 60 degrees Celsius, and 32 A at up to 70 degrees Celsius with 10 mm² conductor cross section. AC-3 rated operational current is 26 A at 220 to 240 V, 380 to 400 V and 415 V, 26 A at 440 V, 23 A at 500 V and 17 A at 690 V. AC-3 rated operational power is 6.5 kW at 220 to 240 V, 11 kW at 380 to 400 V and 415 V, and 15 kW at 440, 500 or 690 V for three-phase motors at the listed speeds.
UL and NEMA Ratings
NEMA size is 1, with NEMA continuous amp rating thermal current of 27 A. NEMA maximum horsepower ratings are 2 hp at 115 V AC single phase and 3 hp at 230 V AC single phase; for three-phase 60 Hz operation, 7.5 hp at 200 V AC, 7.5 hp at 230 V AC, 10 hp at 460 V AC and 10 hp at 575 V AC. UL general use rating is 45 A at 600 V AC. UL three-phase motor ratings are 7.5 hp at 200 to 208 V AC, 7.5 hp at 220 to 240 V AC, 15 hp at 440 to 480 V AC and 20 hp at 550 to 600 V AC. UL motor amp ratings include 25.3 A at 200 to 208 V, 22 A at 220 to 240 V, 21 A at 440 to 480 V and 22 A at 550 to 600 V.
Coil and Control Circuit
The AF26Z-30-11-21 coil operates at 24 to 60 V AC at 50 or 60 Hz and 20 to 60 V DC. The Z variant is designed for low pull-in and holding consumption, particularly for AC control circuits. The 24 to 60 V coil allows direct control by a 24 V DC 500 mA PLC output according to the AF26Z product documentation. AFZ contactors withstand short voltage dips and voltage sags and comply with SEMI F47-0706. AF contactors include built-in surge protection and do not require additional surge suppressors. The electronic coil interface provides reduced consumption and extended operating limits for worldwide control voltages.
Built-in Auxiliary Contacts
The 2-stack contactor is mounted with a non-removable auxiliary contact block. Built-in auxiliary contacts are one NO and one NC, with mechanically linked contacts compliant with Annex L of IEC 60947-5-1. Auxiliary contact rated operational voltage maximum is 690 V, conventional free-air thermal current is 16 A at up to 40 degrees Celsius, and rated frequency limits are 25 to 400 Hz. AC-15 rated operational current is 6 A at 24 to 127 V 50 or 60 Hz, with lower making and breaking capacity at higher voltages. DC-13 ratings range from 6 A at 24 V DC to 0.13 A at 500 V DC. Non-overlapping time between NO and NC contacts is at least 2 ms.
Construction and Wiring
The AF26Z is a two-stack three-pole contactor with screw terminals. Main conductor connection capacity ranges from rigid solid 1 by 2.5 to 10 mm², stranded 2 by 2.5 to 10 mm², flexible with or without ferrules in the listed ranges, and UL or CSA capacity of 1 or 2 by AWG 14 to 8 for main poles. Auxiliary and control terminal capacity is smaller, with coil terminal torque 1.2 Nm or 11 lb-in. The contactor mounts on a 35 by 7.5 mm or 35 by 15 mm rail according to IEC 60715 and EN 60715, using two diagonally placed M4 screws. Contact weight is approximately 0.390 kg.
Standards and Compliance
The AF26Z-30-11-21 complies with IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, UL 508 and CSA C22.2 No. 14 according to the ABB documentation. The contactor meets the listed utilization categories, auxiliary contact standards and NEMA or UL ratings for industrial motor and load switching. Climatic withstand is category B according to IEC 60947-1 Annex Q.
Typical Application Scenarios
Typical applications include three-phase motor starters, pumps, fans, compressors, conveyors, machine tools, packaging machines, material handling equipment, small industrial machinery, non-inductive resistive loads and slightly inductive loads. The 24 to 60 V AC or DC coil and low-consumption Z design suit PLC-controlled panels, automation cabinets and systems where control voltage variations or short voltage sags must be tolerated. The contactor is commonly combined with an overload relay for motor branch protection.
Installation and Wiring Notes
Installation should follow the ABB AF26 contactor documentation, IEC or EN 60947-4-1 motor starter standards, UL or CSA requirements where applicable, and local electrical codes. Mount the contactor on DIN rail or panel, connect line and load main contacts to the three-phase supply and motor, wire the coil control circuit to the rated 24 to 60 V AC or 20 to 60 V DC supply, and connect the NO and NC auxiliary contacts to the control or feedback circuit. Verify contactor rating against motor current and horsepower, coordinate with the overload relay or motor protection device, and check terminal torque, wiring capacity and load type before energizing.
Advantages and Selection Notes
The AF26Z-30-11-21 offers three main NO poles, one NO and one NC built-in auxiliary contact, 45 A AC-1 current, 26 A AC-3 current, 11 kW at 400 V AC-3 rating, 15 hp at 480 V UL rating, 24 to 60 V AC or 20 to 60 V DC low-consumption coil, direct 24 V DC PLC output compatibility, SEMI F47 sag tolerance, built-in surge protection and screw terminals. When selecting a replacement, confirm pole count, main and auxiliary contact configuration, AC-1 or AC-3 rating, voltage, kW or horsepower, coil control voltage and polarity where DC is used, terminal type and overload relay coordination. The AF26Z-30-11-21 is a power contactor, not a breaker, overload relay, soft starter, drive, PLC or sensor; its role is to switch and control three-phase motor and industrial loads under control circuit command.
Get a Quote