MVI56-103M
Description

1. Product Overview
Model: MVI56‑103M
Manufacturer: ProSoft Technology (Rockwell Automation partner)
Platform: Allen‑Bradley ControlLogix (1756 chassis, single‑slot)
Protocol: IEC 60870‑5‑103 Master (power system protection/control standard)
Function: Enables ControlLogix PLCs to act as an IEC 103 master, communicating with protection relays, substation IEDs, and field devices in electrical substations.
Data Exchange: High‑speed backplane data transfer between module and ControlLogix tags; supports telemetry, SOE, fault records, and time synchronization.
2. Key Features
Dual independent master ports (P1, P2), plus CFG debug/config port
Port hardware: RS‑232/422/485 (software selectable), electrical isolation
Max devices: Up to 32 IEC 103 slaves total across two ports
Protocol services:
Master polling: Cyclic data acquisition (YX, YC, YM)
Event handling: SOE (Sequence of Events), time‑stamped reports
Controls: Remote commands, parameter setting
File transfer: Fault records, disturbance data
RTC & CMOS backup: 21‑day battery backup (non‑replaceable)
Diagnostic LEDs: PWR, RUN, BP LINK, P1 ACT, P2 ACT
Approvals: CE, UL/cUL, CSA, ATEX, RoHS
3. Technical Specifications
General
Slot usage: 1 slot (1756 local/remote rack)
Backplane current: 800 mA @ 5 VDC; 3 mA @ 24 VDC
Data mapping: Direct tag‑based access (no M0/M1 files)
Configuration: ProSoft Configuration Builder (PCB)
Serial Communication (P1/P2)
Standards: IEC 60870‑5‑103, RS‑232/422/485
Baud rate: 110–115.2 kbps
Data bits: 8; Parity: Even/Odd/None; Stop bits: 1/2
Connector: RJ45 (P1, P2, CFG)
Environmental
Operating temp: 0°C to +60°C (32°F to 140°F)
Storage temp: ‑40°C to +85°C
Humidity: 5%–95% non‑condensing
Vibration: 5 g (10–150 Hz)
Shock: 30 g (operational)
4. LED Indicators
PWR: On = backplane power OK
RUN: On = module operational; flashing = firmware activity
BP LINK: On = backplane communication active
P1 ACT / P2 ACT: Flashing = data traffic on port 1/2
5. Installation & Configuration
Power off ControlLogix chassis.
Insert MVI56‑103M into empty 1756 slot.
Connect IEC 103 devices to P1/P2; connect PC to CFG port.
Power on; verify module in Studio 5000.
Use ProSoft Configuration Builder (PCB) to define:
Port parameters (baud, parity, protocol)
Slave addresses (1–32)
Data mapping (IEC 103 objects ↔ ControlLogix tags)
Download configuration and test communication.
6. Applications
Power substations: Connect ControlLogix to IEC 103 protection relays, breakers, IEDs
SCADA integration: Telemetry (YX/YC/YM), SOE, fault data collection
Legacy system modernization: Migrate old IEC 103 networks to ControlLogix
Distributed power: Wind/solar farm device monitoring
Industrial automation: Process control with IEC 103‑compliant devices
7. Advantages
Dual‑port master: Two independent networks, flexible topology
Power protocol expertise: Full IEC 103 compliance for protection/control
Time‑critical data: High‑precision time stamping for SOE/events
Robust isolation: Protects against ground loops and EMI in substations
Seamless Rockwell integration: Native tag access, no intermediate logic
Get a Quote