ILX34-MBS485
May 18, 2026

ILX34-MBS485

Model: ILX34‑MBS485 (ProSoft Technology) Type: Industrial serial communication module Form Factor: 1734 POINT I/O format (single‑wide, 12 mm) Host Systems: • Allen‑Bradley 1734 POINT I/O adapters • CompactLogix L1 processors (5370 L1) Function: Bridges EtherNet/IP (Logix side) ↔ Modbus RTU over RS‑485 (field devices) Role: Configurable as Modbus Master or Slave

Description

ILX34-MBS485.jpg

1. Product Overview

  • Model: ILX34‑MBS485 (ProSoft Technology)

  • Type: Industrial serial communication module

  • Form Factor: 1734 POINT I/O format (single‑wide, 12 mm)

  • Host Systems:

    • Allen‑Bradley 1734 POINT I/O adapters

    • CompactLogix L1 processors (5370 L1)

  • Function: Bridges EtherNet/IP (Logix side) ↔ Modbus RTU over RS‑485 (field devices)

  • Role: Configurable as Modbus Master or Slave

2. Key Features

  • RS‑485 half‑duplex, 2500 Vrms isolation

  • Modbus RTU: Master/Slave selectable; supports Function Codes 01–06, 15, 16

  • Master capacity: Up to 31 slaves; 30 commands per scan; 35 words/command

  • Data size: Up to 1000 words (input/output)

  • Baud rate: 1200–115200 bps (software configurable)

  • Serial params: 7/8 data bits, 1/2 stop bits, No/Odd/Even parity

  • Diagnostics: Live status in controller tags; per‑node health monitoring

  • Control: Serial port enable/disable via ladder logic

  • Configuration: Saved in CompactLogix ACD project; uses standard Studio 5000 AOP/AOI

  • Distance: Up to 4,000 ft (1219 m) on RS‑485

3. Specifications

Interface

  • Serial: 1× RS‑485 (terminal block)

  • Protocol: Modbus RTU (Master/Slave)

  • Isolation: 2500 Vrms

Power

  • Input: 5 VDC (from POINT I/O backplane)

  • Current: ~75 mA

Environmental

  • Operating Temp: 0°C to +55°C (32°F to 131°F)

  • Storage Temp: ‑40°C to +85°C

  • Humidity: 5%–95% non‑condensing

  • Shock/Vibration: 30 g operational; 5 g @ 10–500 Hz

Physical

  • Dimensions: 56 × 12 × 75.5 mm (H × W × D)

  • Weight: ~0.1 kg

  • Mounting: DIN rail (via POINT I/O base)

4. LED Indicators

  • PWR: Green = backplane power OK

  • STAT: Green = running; Red = fault

  • TXD/RXD: Green flashing = serial activity

  • LINK: EtherNet/IP connection status (via host adapter)

5. Typical Applications

  • Connect Modbus RTU meters, drives, sensors to Rockwell Logix

  • SCADA & remote field device interface

  • Water/wastewater, energy, material handling

  • Retrofits: add Modbus to existing POINT I/O systems

6. Advantages

  • Native Logix integration: No gateway PC; config in Studio 5000

  • Master/Slave flexibility

  • Long‑distance RS‑485 (1.2 km)

  • Compact: single‑wide POINT I/O, saves cabinet space

  • Industrial isolation & wide temp


Get a Quote