AN-X-PB2
Description
1. Product Overview
Model: AN-X-PB2 (ProSoft Technology)
Function: DIN‑rail, bidirectional protocol gateway
EtherNet/IP ↔ PROFIBUS DP
Purpose: Lets Allen‑Bradley EtherNet/IP PLCs (ControlLogix/CompactLogix)
connect, monitor, and control PROFIBUS DP slave devices without replacing existing field I/O.
2. Key Features
EtherNet/IP Side
10/100 Mbps Ethernet (RJ45)
Up to 15 scheduled connections
RPI: 2–750 ms
Data mapped directly to RSLogix 5000 tags
Explicit messaging supported
PROFIBUS DP Side
DP‑V0/V1 Master (slave mode optional)
Supports up to 31 PROFIBUS DP slaves
Baud rate: 9.6 kbps – 12 Mbps
Data size:
Input: up to 500 words
Output: up to 248 words
Standard PROFIBUS cable, terminal block
General
Embedded web server (config via browser)
MicroSD slot: backup/restore config, firmware update
Operating modes: Master (MAS), Slave (SLV), Monitor (MON)
Industrial temp: 0°C to +50°C
Certifications: CE, UL, RoHS
3. Specifications
Power
12–24 VDC, 100 mA @ 24 VDC, ≤ 2.4 W
Physical
35 mm DIN rail, approx. 110 × 75 × 40 mm, IP30
Interfaces
Ethernet: 10/100 Mbps, RJ45
PROFIBUS DP: terminal block (shielded cable required)
4. LED Indicators
PWR: solid = power OK
NET: flashing = EtherNet/IP active
PB: flashing = PROFIBUS DP active
STS: system status
ERR: on = fault (comm/config)
5. Installation & Wiring
Mount on DIN rail in cabinet.
Connect 12–24 VDC (observe polarity).
Connect Ethernet to EtherNet/IP controller network.
Wire PROFIBUS DP bus to terminal block:
Use shielded twisted pair
Terminate bus at both ends (120 Ω)
Set gateway IP via web (default: 192.168.1.100).
Scan PROFIBUS slaves, map I/O to EtherNet/IP tags.
Save config and reboot.
6. Operating Modes
Master (MAS): full DP master, polls slaves, controls I/O
Slave (SLV): acts as DP slave to a higher‑level DP master
Monitor (MON): listen‑only, diagnose DP traffic
7. Application
Integrate PROFIBUS DP devices into EtherNet/IP systems
Migrate legacy PROFIBUS systems to Rockwell Automation platforms
Process industries: manufacturing, automotive, water/wastewater, energy
8. Safety Notes
Wiring only when powered off
Use shielded cable for PROFIBUS DP; proper grounding
Bus termination must be correct (120 Ω at both ends)
Avoid high humidity, dust, strong EMI
Installation/configuration by qualified personnel
Get a Quote