3701
May 18, 2026

3701

TRICONEX 3701 is a 32-channel differential analog input module with triple modular redundancy (TMR). Designed for Tricon V9/V10/V11 SIS safety systems, it accepts 0–10VDC field signals (also 4–20mA via 500Ω shunt), providing high accuracy and SIL3 compliance for higher‑voltage analog sensing loops.

Description

3701.jpg

3701(5.jpg

3701(4.jpg

3701(3.jpg

3701(2.jpg

TRICONEX 3701

32Ch 0–10VDC TMR Analog Input Module

English Specification (No Images)

1. General Description

TRICONEX 3701 is a 32-channel differential analog input module with triple modular redundancy (TMR). Designed for Tricon V9/V10/V11 SIS safety systems, it accepts 0–10VDC field signals (also 4–20mA via 500Ω shunt), providing high accuracy and SIL3 compliance for higher‑voltage analog sensing loops.

2. Basic Information

  • Model: 3701

  • Type: 32Ch Differential Analog Input (TMR)

  • Signal Range: 0–10VDC / 4–20mA (500Ω shunt)

  • System Compatibility: Tricon V9 / V10 / V11

  • Safety Level: SIL3 (IEC 61508 / IEC 61511)

  • Certifications: TUV, FM, CSA, ATEX/IECEx

  • Architecture: TMR, 2oo3 voting

  • Status: In production & supported

3. Key Features

  • 32 differential channels, 4‑wire, DC‑coupled

  • 12‑bit resolution, high linearity

  • TMR fault tolerance, 2oo3 voting logic

  • Channel‑to‑ground isolation: 1,500VDC

  • Diagnostics: open/short circuit, out‑of‑range, TMR mismatch, module health

  • Update time: <55ms

  • Hot‑swappable; online replacement

  • High noise immunity: –80dB common‑mode rejection (DC–100Hz)

  • Overvoltage protection: 150VDC / 115VAC continuous

4. Technical Parameters

4.1 Analog Input

  • Voltage: 0–10VDC

  • Current: 4–20mA (external 500Ω shunt)

  • Channels: 32, differential, isolated

  • Resolution: 12 bits

  • Accuracy: ±0.15% FSR (0°C to 60°C)

  • Input impedance: >1MΩ (voltage)

  • Update rate: <55ms

4.2 Safety & Isolation

  • Voting: 2‑out‑of‑3 (2oo3)

  • Fault coverage: ≥99%

  • Isolation: 1,500VDC (channel–ground)

  • Diagnostics: open/short, over/under‑range, TMR mismatch

4.3 Environmental

  • Operating temp: –40°C to +70°C

  • Storage temp: –40°C to +85°C

  • Humidity: 5%–95%, non‑condensing

  • Vibration: 5–200Hz, 2G

4.4 Power & Mechanical

  • Backplane: 5VDC

  • Power consumption: ≤15W

  • Dimensions: 178 × 127 × 63mm

  • Weight: ~0.8kg

5. Function

Acquires 0–10VDC or 4–20mA signals from transmitters/sensors; converts to digital; validates via TMR voting; sends to main controller. Supports SOE and process data logging.

6. LED Indicators

  • PWR (Green): Power OK

  • RUN (Green): Normal operation

  • FAULT (Red): Module/channel fault

  • CH (Yellow): Channel active

7. Installation & Configuration

  1. Insert into Tricon I/O slots

  2. Wire 0–10VDC or 4–20mA (500Ω shunt) to terminal base

  3. Configure ranges/diagnostics via TriStation 1131

  4. Verify LEDs and data quality

8. Typical Applications

  • Pressure, temperature, level, flow monitoring (SIL3, 0–10V transmitters)

  • ESD/SIS analog sensing loops (higher voltage)

  • BMS combustion parameters

  • Oil/gas, chemical, power plant safety instrumentation

9. Maintenance

  • Hot swap faulty modules online

  • Calibrate annually or per site procedure

  • Check wiring/shunts periodically

  • Review fault/SOE logs

10. Compatibility

  • Terminal base: 3701TB series

  • Software: TriStation 1131

  • Compatible processors: 3008, 3005 series


Get a Quote