Product Description 3636R is dedicated terminal base matching 3636 main relay output card, simplex non-TMR 32-channel independent isolated SPDT dry contact terminal seat for Tricon SIS rack, field wir
June 03, 2026

Product Description 3636R is dedicated terminal base matching 3636 main relay output card, simplex non-TMR 32-channel independent isolated SPDT dry contact terminal seat for Tricon SIS rack, field wir

Product Description 3636R is dedicated terminal base matching 3636 main relay output card, simplex non-TMR 32-channel independent isolated SPDT dry contact terminal seat for Tricon SIS rack, field wiring termination carrier for mechanical relay output, support external terminal block wiring, hot-plug compatible with Tricon standard chassis。

Description

Model Interpretation

3636R:Termination base for 3636 relay output module; suffix R=Relay terminal base; single-slot installation, exclusively paired with main board 3636; incompatible with transistor DO series like 3624/3664/3667; fits 8110/8111/8112/8115/8116 Tricon backplane rack。

Technical Parameters

Electrical Spec

Channel:32 fully isolated non-commoned SPDT (Form C) relay contact terminals

Rated contact spec:Max 125VAC/155VDC, single point resistive load 2A max, min drive load 10mA@5VDC

Per-channel independent 2.5A fast fuse integrated on base terminal

Field-to-backplane isolation:1500VDC galvanic isolation per channel

Backplane power supply from Tricon rack 24VDC, base power consumption<9W

Safety & Mechanical

Simplex non-triplicated architecture, no TMR voting on base side; main card 3636 realizes channel diagnostic readback via base wiring

Dimension(W×H×D):115×32×192mm, net weight≈0.78kg, single slot 3U standard Tricon form factor

Ambient working:−40℃~+70℃, storage −55℃~+85℃, 5%~95%RH non-condensing

Front PCB reserved signal lead-out to external termination panel(ETP) via flat cable

Core Functions

Field cable centralized termination for 3636 relay output card; independent channel fuse protection against field short-circuit; relay contact status feedback wiring for per-channel open/closed readback diagnosis; online hot swap main module without disconnect field wiring; transition wiring between controller backplane and field equipment。

Application Scenarios

Oil&gas plant non-safety alarm horn, site indicator lamp control; refinery auxiliary interlock relay drive; power plant BMS auxiliary annunciator circuit; chemical factory non-critical bypass solenoid switching; F&G system secondary alarm output loop。

Model Distinction

3636R:Terminal base for 3636 32-point relay DO |3664R:Base for 3664 32-point sourcing transistor DO |3667R:Base for 3667 supervised transistor DO

Dry contact relay dedicated base |Non-supervised transistor output base |Supervised safety transistor output base