TRICONEX 3611E TMR Supervised 115VAC Digital Output Module
Description
Model Interpretation
3611E: 8Ch isolated supervised 115VAC TMR DO; E = enhanced diagnostic version; exclusive mating terminal:3611R; AC safety output, different from 24VDC transistor/relay DO series.
Technical Parameters
Electrical Spec
Channel:8 fully isolated non-common AC output
Nominal field:115VAC (90~132VAC operating range, 50/60Hz)
Single channel continuous:0.5A, surge 3.5A/10ms; min load ≥25mA for open-circuit supervision
Off-state leakage ≤3.5mA; independent channel fuse fitted on 3611R base
Field-to-backplane isolation:2000VAC galvanic isolation
Backplane power ≤11W; auto short-circuit recovery protection
Safety & Redundancy
Architecture:TMR 2oo3 hardware voting; single branch fault avoids spurious trip/fail-to-shutdown
Certification:IEC61508 SIL3, TÜV, UL, CE, FM, ATEX
Diagnostics:per-channel pulse test + load readback, detect wire break, open load & short; fault coverage>99.9%
SOE ≤40ms; MTBF>133000H
Mechanical & Environment
Single slot 3U module; dimension 114×30×185mm; weight≈1.12kg; ivory front panel
Operating:−40℃~+70℃; storage −55~+85℃; humidity 5%~95%RH non-condensing
LED indicators: PASS, FAULT, ACTIVE, LOAD
Core Functions
Supervised 115VAC safety drive for critical AC solenoid/shutdown relays; non-intrusive periodic pulse check confirms field loop integrity without unintended valve action; TMR redundant circuit ensures SIL3 safety requirement; online hot swap without system halt; fault info uploaded to TriStation for troubleshooting.
Applications
Offshore/onshore oil&gas 115VAC ESD shutdown solenoid control; refinery HIPPS AC cut-off valve drive; petrochemical flare safety interlock; power plant boiler/turbine AC trip relay output; F&G fire suppression AC actuator control.
Brief Comparison
3611E:8Ch isolated supervised 115VAC DO |3627:16Ch sink supervised 120VDC DO |3623:16Ch non-supervised 120VAC/DC DO
Isolated AC safety output |High voltage DC safety output |General auxiliary AC/DC output