TRICONEX 3667 TMR 32CH Common-Source Supervised 24VDC Digital Output Module
Description
Model Interpretation
3667:32-channel commoned source-type supervised 24VDC DO; matched terminal base:3667R; single-slot hot-swappable; compatible with 8110/8111/8112/8115/8116 standard Tricon chassis; supervised high-density counterpart of non-supervised 3664, 16-point supervised peer:3624。
Technical Parameters
Electrical Spec
Channel quantity:32 commoned sourcing digital transistor output
Rated field voltage:24VDC, operating range 22~30VDC, max 36VDC transient
Per-channel continuous rated:0.5A DC, inrush surge 10A/10ms for inductive coil load
Full per-channel supervision: open-circuit, short-circuit, load missing online diagnosis, independent channel fuse protection on terminal board
Field-backplane galvanic isolation:1500VDC
Backplane power consumption<15.2W
Safety & Redundancy
Architecture:Full TMR triple-path 2-out-of-3 hardware voting, single path fault cannot trigger spurious trip
Certification:IEC61508 SIL3, TÜV, UL, FM, CE safety approval
Diagnostic range:Module internal hardware fault + per-channel field circuit full monitoring; fault coverage>99%
SOE event timestamp ≤40ms; MTBF>132000 operating hours
Mechanical & Environment
Single slot 3U standard Tricon module, black front panel
Dimension(W×H×D):115×32×190mm, net weight≈0.85kg
Operating ambient:−40℃~+70℃; storage −55℃~+85℃; humidity 5%~95%RH non-condensing
Front panel LED: PASS, FAULT, group channel status indicator
Core Functions
High-density 32-point safety-grade common-source output for critical field loads; full loop supervision detects wire breakage, coil burnout and short fault; TMR redundant structure satisfies SIS cabinet SIL3 specification; online hot plug replacement without system shutdown; centralized wiring reduces field cable workload; parameter configuration via TriStation software。
Application Scenarios
Oil&gas plant ESD critical solenoid shutdown control; refinery safety interlock relay cluster drive; power plant turbine trip auxiliary safety circuit; chemical factory emergency cut-off valve control; LNG terminal fire&gas safety shutdown output。
Model Distinction
3667:32Ch source supervised 24V DO |3664:32Ch source non-supervised 24V DO |3624:16Ch source supervised 24V DO
High-density safety critical output |High-density non-critical auxiliary output |16-point small-scale safety output
Get a Quote