2755
Description


TRICONEX 2755
Analog Input Module (TMR, SIL3)
Official English Specification (consistent format: 2651/2652/2658/2700/2750)
1. General Description
2. Model Information
Model: 2755
Type: Analog Input Module (TMR)
System Series: Triconex Tricon / Trident SIS
Safety Level: SIL3 (IEC 61508)
Certification: TÜV, FM, CSA
Part Number: 2755‑010
Status: Active / In production
3. Main Features
Triple Modular Redundancy (TMR): 3 independent input circuits, 2oo3 voting
16‑Channel Analog Input: 4–20mA (default) / 0–10V configurable
High Precision: 16‑bit resolution, ±0.1% full‑scale accuracy
Full Channel Diagnostics: Open/short circuit, over‑range, under‑range detection
Hot‑Swappable: Online replacement without system shutdown
Galvanic Isolation: Channel‑to‑backplane 1500Vrms
SOE Timestamps: 1ms resolution for process event logging
Noise Rejection: EMI/RFI filtering, common‑mode rejection
4. Technical Parameters
4.1 Input Specifications
Signal Type: 4–20mA (default), 0–10V (configurable)
Number of Channels: 16
Resolution: 16‑bit
Accuracy: ±0.1% FS (25°C)
Repeatability: ±0.05% FS
Input Impedance: 250Ω (4–20mA); >1MΩ (0–10V)
Isolation: 1500Vrms channel‑to‑backplane
Response Time: ≤100ms per channel
4.2 Redundancy & Safety
Architecture: TMR (3 independent channels)
Voting: 2oo3 fault‑tolerant
Diagnostic Coverage: >99%
System Availability: 99.999%
4.3 Environmental
Operating Temperature: 0°C to +60°C
Storage Temperature: −40°C to +85°C
Relative Humidity: 5%–95% non‑condensing
Vibration: 5–200Hz, 1g
4.4 Power & Physical
Backplane Power: 5VDC
Power Consumption: ≤12W
Dimensions: Standard Trident full‑size module
Weight: ~1.2kg
5. Function Overview
Acquires 16‑channel 4–20mA/0–10V analog signals from transmitters (pressure, temperature, level, flow)
Three TMR channels sample independently; 2oo3 voting ensures valid data
Diagnostics continuously monitor for faults and report to TriStation
Supports SOE for time‑stamped process events
Integrates with Trident CPU (e.g., 2750) for safety logic execution
6. LED Indicators
PWR (Green): 5VDC backplane power OK
RUN (Green): Module active, TMR sync normal
FAULT (Red): Channel/module fault or voting mismatch
CH (Yellow): Per‑channel status (active/fault)
7. Installation & Configuration
Insert 2755 into empty Trident baseplate slot
Connect 4–20mA/0–10V field transmitters to FTA terminal base
Use TriStation 1131 to set signal type, range, filtering, and SOE
Verify: PWR+RUN green; no FAULT red; CH LEDs reflect active channels
8. Typical Applications
ESD: Pressure, temperature, level transmitter monitoring
BMS: Flame temperature, fuel gas pressure analog inputs
FGS: Gas concentration detector (4–20mA) monitoring
Critical process: Reactor temperature, vessel pressure, flow safety loops
Power plant: Steam turbine vibration, temperature, pressure safety inputs
9. Maintenance
Hot‑swap faulty 2755 without downtime
Inspect field wiring and FTA terminal connections
Review fault logs and SOE via TriStation
Compatible with Trident TMR CPU 2750
10. Compatibility
Compatible Systems: Triconex Tricon, Trident SIS
Configuration Software: TriStation 1131 (v4.0+)
Matching Terminal Base: 16‑channel analog input FTA
Model: 2755
Description: 16‑Channel Analog Input Module (4–20mA/0–10V), TMR, SIL3
Get a Quote