2750
May 18, 2026

2750

TRICONEX 2750 is a TMR programmable control module for Triconex Trident / Tricon SIS. It acts as a safety logic controller with triple processors, executing user-defined safety applications in SIL3 loops. It supports both digital/analog I/O and multi-protocol communications, commonly used as a standalone safety controller or co-processor in ESD/BMS/FGS systems.

Description

2750.jpg

TRICONEX 2750

Programmable Control Module (TMR, SIL3)

Official English Specification Manual (consistent format with 2651/2652/2658/2700)

1. General Description

TRICONEX 2750 is a TMR programmable control module for Triconex Trident / Tricon SIS. It acts as a safety logic controller with triple processors, executing user-defined safety applications in SIL3 loops. It supports both digital/analog I/O and multi-protocol communications, commonly used as a standalone safety controller or co-processor in ESD/BMS/FGS systems.

2. Model Information

  • Model: 2750

  • Type: Programmable Control Module (TMR CPU)

  • System Series: Triconex Tricon / Trident SIS

  • Safety Level: SIL3 (IEC 61508)

  • Certification: TÜV, FM, CSA

  • Part Number: 3000105‑010

  • Status: Active / In production

3. Main Features

  • Triple Modular Redundancy (TMR): 3 independent processors, 2oo3 voting

  • User Programmable: Supports C‑language & IEC 61131‑3 (TriStation 1131)

  • Large I/O Capacity: Max 256 inputs / 128 outputs (digital+analog)

  • Multi‑Protocol Communication: Modbus RTU/TCP, Ethernet, RS‑232, RS‑485

  • Deterministic Execution: Fixed scan rate (1–10ms) for safety logic

  • Full Diagnostics: Self‑test, fault isolation, voting mismatch alarm

  • SOE Timing: 1ms resolution sequence‑of‑events logging

  • Hot‑Swappable: Online replacement without shutdown

4. Technical Parameters

4.1 CPU & Performance

  • Architecture: 3× 32‑bit RISC processors (TMR)

  • Execution Rate: 1ms–10ms configurable scan

  • Memory: 8MB program / 8MB data (redundant)

  • Programming: C‑language, LD/FBD/ST (TriStation 1131)

4.2 I/O Capacity

  • Digital Inputs: 256 max (24VDC)

  • Digital Outputs: 128 max (24VDC/relay)

  • Analog Inputs: 64 max (4–20mA / 0–10V)

  • Analog Outputs: 32 max (4–20mA / 0–10V)

4.3 Communication

  • Ports: 2× Ethernet, 2× RS‑485, 1× RS‑232

  • Protocols: Modbus TCP/RTU, Tricon Peer‑to‑Peer

  • Speed: Ethernet 10/100Mbps; RS‑485 115.2kbps

4.4 Redundancy & Safety

  • Architecture: TMR (3‑channel independent)

  • Voting: 2oo3 fault‑tolerant

  • Diagnostic Coverage: >99%

  • System Availability: 99.999%

4.5 Environmental

  • Operating Temperature: −20°C to +60°C

  • Storage Temperature: −40°C to +85°C

  • Relative Humidity: 5%–95% non‑condensing

  • Vibration: 5–200Hz, 1g

4.6 Power & Physical

  • Backplane Power: 5VDC / 3.3VDC

  • Power Consumption: ≤25W

  • Dimensions: 197mm × 287mm × 170mm

  • Weight: ~4.5kg

5. Function Overview

  • Executes SIL3 safety logic for ESD, BMS, FGS, and interlocks

  • Processes up to 256 inputs / 128 outputs (digital+analog)

  • Performs 2oo3 voting on all internal logic and I/O data

  • Communicates with DCS, HMI, and other SIS nodes via multi‑protocol ports

  • Logs SOE with 1ms resolution for incident analysis

  • Supports redundant 2750 pairs for high‑availability systems

6. LED Indicators

  • PWR (Green): 5VDC backplane power OK

  • RUN (Green): Module active, TMR sync normal

  • FAULT (Red): CPU/voting/I/O fault

  • COMM (Yellow): Network activity

  • FORCE (White): I/O forced state active

7. Installation & Configuration

  1. Insert 2750 into Trident baseplate CPU slot

  2. Connect Ethernet/serial cables to front‑panel ports

  3. Use TriStation 1131 to:

    • Download safety logic (C or IEC 61131‑3)

    • Configure I/O mapping & communication

    • Set scan rate (1–10ms) & fault thresholds

  4. Verify: PWR+RUN green; no FAULT red; COMM flashes on traffic

8. Typical Applications

  • ESD Emergency Shutdown Systems (oil & gas, petrochemical)

  • BMS Burner Management Systems (power, refining)

  • FGS Fire & Gas Systems (process plants)

  • Turbine/Generator Safety Controllers (power)

  • SIL3 Safety Interlock Controllers (chemical, pharmaceutical)

9. Maintenance

  • Hot‑swap faulty 2750 without downtime

  • Check Ethernet/serial cables and port LEDs

  • Review fault logs & SOE via TriStation

  • Keep firmware updated for latest diagnostics

10. Compatibility

  • Compatible Systems: Triconex Tricon, Trident SIS

  • Configuration Software: TriStation 1131 (v4.0+)

  • Matching I/O Modules: 2700 (DI), 2701 (DO), 2751 (AI), 2752 (AO)

  • Model: 2750

  • Description: TMR Programmable Control Module, SIL3, 256In/128Out, Multi‑Protocol


Get a Quote