PM6301A
Description
I. Core Positioning
PM6301A is the core power supply module for the Tricon system rack, installed in the power slot of the main rack / expansion rack; it adopts a dual-redundancy design, operating in parallel with another PM6301A for hot standby, responsible for converting a wide range of input voltage (100–240VAC or 24–125VDC) into a stable 24VDC (±1%) for all rack loads, serving as the power lifeline for the uninterrupted operation of the SIS system.
II. Specifications (Official Standard Version)
1. Input (Wide Range Compatibility)
AC: 100–240VAC, 50/60Hz, ±10%
DC: 24–125VDC, ±10%
Input Current: Typical 2.5A@120VAC, 1.2A@240VAC
Surge Current: ≤15A (Cold Start)
2. Output (Stabilized Isolation)
Output Voltage: 24VDC (±1% Accuracy)
Output Current: 10A Continuous (Single Module), Redundant Parallel Can Be Expanded
Power: 240W Maximum
Efficiency: ≥95% (Full Load), Low Heat Generation
Isolation: Input - Output 1500VAC Isolation, Anti-Surge / Static Electricity
Ripple Noise: ≤50mVpp
3. Redundancy and Reliability
Architecture: Dual Module Redundancy (1+1), Hot Swap, No Disturbance Switching
Current Sharing: Active Current Sharing, Load Balance, Fault Automatic Switching
MTBF: ≥500,000 Hours (25℃)
Diagnosis: Overvoltage, Undervoltage, Overcurrent, Short Circuit, Over Temperature Real-time Self-Diagnosis
4. Protection Characteristics
Overvoltage: Output 28VDC Clamping, Input 265VAC Protection
Undervoltage: Input 85VAC/20VDC Alarm, 75VAC/18VDC Shutdown
Overcurrent: 12A Limiter, Short Circuit Protection, Automatic Recovery
Over Temperature: 85℃ Rating Reduction, 100℃ Shutdown, Temperature Drop Automatic Recovery
5. Electrical and Environmental
Power Consumption: Standby 15W, Full Load 25W
Operating Temperature: -40℃ ~ +70℃ (Wide Temperature, SIS Standard)
Storage Temperature: -55℃ ~ +85℃
Humidity: 5%–95%, No Condensation
Vibration: 10–150Hz, 0.1g Sinusoidal
Certifications: TÜV SIL3, CE, UL, CSA, ATEX/IECEx
6. Mechanical and Indicator Lights
Size: 267 × 166 × 50mm (Standard Tricon I/O Size)
Weight: Approximately 1.8kg
Installation: Rack Power Slot, Hot Swap
Indicator Lights:
PWR (Green): Output Normal
INPUT (Green): Input Valid
FAULT (Red): Fault / Alarm
REDUND (Yellow): Redundancy Synchronization
Get a Quote