HCU3700
Description
I. Core Positioning
HCU3700 is a TMR analog input module with HART functionality, not an FTA terminal board, directly plugged into the Tricon rack, and used in conjunction with FTA-554; it supports 4–20mA + HART intelligent transmitters, capable of simultaneously collecting analog and digital HART data. It is the preferred choice for SIS system intelligent instrument integration.
II. Specification Parameters (Official Standard Version)
1. Channels and Signals
Channels: 8 isolated analog input (AI), TMR triple redundancy
Signals: 4–20mA (with HART), 0–20mA, 0–5V, 0–10V, ±10V
Resolution: 16 bits
Accuracy: ±0.05% FS (analog); HART data 100% transparent
Input Impedance: Current 250Ω; Voltage ≥1MΩ
Isolation: Channel-to-channel 1500VAC, channel-to-backplane 1500VAC
HART: Independent HART modulation per channel, supports HART 5/7, can read/write instrument parameters, diagnostics, range, TAG
2. Electrical and Redundancy
Power Supply: 24VDC (±10%), backplane power supply
Redundancy: TMR triple redundancy architecture, three CPU voting, single channel failure does not affect the system
Diagnosis: Open circuit, short circuit, overrange, HART communication failure, fuse melting
Power Consumption: Approximately 8W
3. Mechanical and Environment
Size: 225 × 112 × 40mm (standard Tricon I/O size)
Weight: Approximately 1.2kg
Installation: Tricon standard I/O rack slot, hot-swappable
Temperature: -40℃ ~ +70℃ (wide temperature range)
Certification: CE, UL, CSA, TÜV SIL3, ATEX (available in explosion-proof areas)
4. Panel and Interface
Inner Side: Backplane bus, TMR triple communication
Outer Side: D-SUB 37-pin, connects FTA-554 terminal board
Indicators:
PWR (green): Module power supply normal
RUN (green): Module running normally
CH1–CH8 (yellow): Channel signal normal
FAULT (red): Module/Channel failure
HART (blue): HART communication active
III. Required Terminal Board
FTA-554: 8-channel isolated AI terminal board, with fuses, surge protection, LED diagnostics, dedicated for 4–20mA + HART wiring on-site.
IV. Typical Applications
SIS/ESD: Intelligent pressure / flow / level / temperature transmitters (HART) signal acquisition
Process: HART feedback for control valves, remote diagnostics and parameter modification of instruments
Safety: SIL3 circuit, open circuit / short circuit / overrange / HART communication failure diagnosis
Intelligent Factory: HART instrument data upload to DCS / upper computer, achieving instrument health management, predictive maintenance
V. Model Distinction (To Avoid Confusion)
HCU3700: 8-channel HART AI, TMR, isolated, SIL3 (mainstream)
HCU3703E: Same as HCU3700, enhanced HART, supports HART 7.1, multi-variable (PV/SV/TV/QV)
AI3401: 8-channel ordinary AI (without HART), isolated, SIL3
AI6503: 8-channel high-precision AI (without HART), wide temperature range, strong anti-interference
Get a Quote