FTA-554
Description
I. Core Explanation (FTA = Field Terminal Assembly)
FTA-554 is the field wiring base for the analog input module:
Placed behind the Tricon AI module, converting the backplane signals into on-site terminals with isolation, fuses, surge protection, and each channel has an independent LED diagnostic for safe system analog input collection.
II. Specification Parameters (Official Standard Version)
1. Channels and Signals
Channels: 8 analog input (AI) channels, fully isolated
Signal range (software selectable): 4–20mA (default), 0–20mA, 0–5V, 0–10V, ±10V
Resolution: 16 bits
Accuracy: ±0.05% FS
Input impedance:
Current: 250Ω
Voltage: ≥1MΩ
Isolation: 1500VAC between channels, 1500VAC between channel and backplane
2. Electrical
Power supply: 24VDC (±10%), backplane feed
Protection: Each channel can be replaced with a 250mA fuse, surge suppression, reverse polarity protection, overcurrent self-recovery
Power consumption: Approximately 5W
3. Mechanical and Environmental
Size: 225 × 112 × 40mm
Weight: Approximately 0.84kg
Installation: Tricon I/O rack slot, paired with the AI module
Temperature: -40℃ ~ +70℃
Certification: CE, UL, CSA, TUV SIL3 (overall certification for the matching module)
4. Panel and Wiring
Inside: D-SUB 37-pin, connects to the Tricon AI module
Outside: Screw terminal block, on-site 4–20mA/0–10V wiring
Indicators (per channel):
PWR (green): Board power supply is normal
CH1–CH8 (yellow): Channel signals are normal
FAULT (red): Fuse blown / open circuit / short circuit
III. Compatible Modules (Must be Paired)
FTA-554 is specifically paired with the Tricon 8-channel isolated AI module:
AI3401: 8-channel 4–20mA/0–10V, isolated, SIL3 (most commonly used)
AI6503: 8-channel high-precision isolated AI, wide temperature range, strong anti-interference
IV. Typical Applications
ESD/SIS: Monitoring of critical process parameters such as pressure, flow, level, and temperature
Process: Feedback of control valves, sensor signal collection
Unit: Monitoring of analog quantities such as vibration, shaft temperature, and speed of compressors / steam turbines
Safety: Analog input for SIL3 circuits, fault detection for open circuit / short circuit / overrange
V. Quick Reference for the Same Series FTA (Avoid Confusion)
FTA-554: 8-channel isolated AI (4–20mA/0–10V), paired with AI3401/AI6503
FTA-544: 4-channel isolated AO, paired with AO3401
FTA-441: 16-channel common-ground terminal board for DI
FTA-442: 16-channel isolated terminal board for DI
Get a Quote