9662-610
Description
I. Product Overview (Core Parameters)
1) Basic Specifications
Model: 9662-610 (24VDC, Commoned, 16 Points)
Signal Type: 24VDC Digital Output (Active DO, Common Terminal)
Channel Count: 16 Points / Board; 32 Points DO Module requires 2 Terminal Boards
Load Voltage: 24VDC ±10%
Single Channel Current: Maximum 1A / Channel; Total Current 16A / Board
Protection: Each Channel 3A Slow-Melting Fuse, with Independent Fuse Fuse Indicator Light
Isolation: ≥1500VAC Field - System Isolation, Anti-Surge, Anti-Interference
Common Terminal: PWR+ / PWR– Global Common Terminal, 16 Points Shared 24VDC Power Circuit
Safety Level: SIL3 (IEC 61508)
Temperature: -40℃ ~ +70℃ (Industrial Wide Temperature)
Certifications: CE, UL, CSA, ATEX/IECEx
Installation: 35mm DIN Rail / Panel Mounting
Compatible Modules: 3624, 3625, 3664, 3674 (Tricon 32 Point 24VDC DO Module)
Connection Cables: Special Flat Cables (e.g. 966x-610 Series Matching Cables)
2) Panel Indicator Lights
CH01–CH16 (Green): Lit when corresponding channel output is connected
PWR (Green): Normal 24VDC Power Supply on Terminal Board
FUSE (Red): Lit when any channel fuse blows (Single Channel Position)
3) Voltage Comparison within the Same Series (9662 Family)
9662-110: 24VDC, 16 Point Relay Output (Dry Contact)
9662-610: 24VDC, 16 Point Common Terminal Active Output (High Current)
9662-910: 120VDC, 16 Point Common Terminal Active Output
II. Usage Instructions (Installation / Wiring / Maintenance)
1) Installation Configuration
32 Point DO Module (3624/3625/3664/3674): 1 Module paired with 2 9662-610 (1–16, 17–32 each 1 Module)
Installation Location: Cabinet DIN Rail, Close to 24VDC Load Side, Shorten High Current Wiring
Hot Swap: Supports Online Replacement, No Shutdown Required
2) Wiring Specifications (24VDC Load Circuit)
Power Side: 24VDC+ → Terminal Board PWR+; 24VDC– → Terminal Board PWR–
Load Side: CHx+ → Load +; Load– → System 24VDC–
Wire Diameter: 1.5–2.5 mm² Multi-strand Copper Wire, Matched with Cold Press Terminal (High Current Circuit Recommended 2.5 mm²)
Fuse: 3A Slow-Melting; FUSE Red Light On Immediately Turns Off and Requires Replacement to Avoid Module Overload
3) Fault Handling
FUSE Lit: Corresponding Channel Short Circuit / Overload → Replace 3A Fuse, Check Load Insulation
CH Unlit: Check Module Output, 24VDC Power Supply, Flat Cable Connection, Load Wiring
PWR Unlit: Check 24VDC Power Supply, Terminal Board Total Fuse, Flat Cable